manualshive.com logo in svg
background image

                                                                                                                                                   

 

- 17- 

4.5 .        System Protection and Error Codes 

If error

unit display―Ex‖ ―Px‖ or―Fx‖

  For example

E2

P5

 

code 

  meaning 

LED2 

remark 

E1 

compressor overheat or discharge 
high temp protection 

   
red and flash 

Decided by outdoor unit 

E2 

  Outdoor air temp sensor error 

Flash 3 times 

Outdoor air temp sensor open circuit or short circuit 

E3 

pipe or return air temp sensor error 

Flash 6 times 

(1)temp sensor open circuit or short circuit   
(2) suck sensor open or short circuit 

E4 

AC return water temp sensor error 

red and flash 

Stop compressor when running AC

 

E5 

AC leaving water temp sensor error 

red and flash 

Stop compressor when running AC

 

E6 

DHW temp sensor error 

red and flash 

Stop compressor when running AC

 

E7 

solar water temp sensor error 

As normal 

Not stop compressor 

E8 

fan coil high temp protection 

red and flash 

Water source anti freeze protection 

E9 

system anti freeze twice 

red and flash 

Stop compressor 

EA 

DHW anti freeze twice 

red and flash 

Stop compressor 

EB 

indoor refrigerant pipe sensor error 

No flash 

Temp sensor open circuit or short circuit 

EC 

water source inlet water sensor error 

No flash 

Temp sensor open circuit or short circuit 

ED 

water source leaving temp sensor 

No flash 

Temp sensor open circuit or short circuit 

EE 

water source anti freeze protection 

No flash 

1.Water source heat exchange not efficient or water source temp 
too low    2.Water source water flow volume not enough 

EF 

water source water flow not enough 

No flash 

Water source water flow volume not enough 

EG 

Indoor ambient sensor error 

No flash 

Temp sensor open circuit or short circuit 

F1 

aaavoltage protection 

Flash 1 time 

Voltage is too high or too low, heat pump will recover when 
voltage be normal (165~265VAC)   

F2 

power module PFC error 

Red and flash 

IPM module error or wire connection wrong 

F3 

compressor abnormal stop   

Red and flash 

  compressor stops abnormally 
 

F4 

outdoor module radiator sensor error 

Flash 5 time 

Temp sensor open circuit or short circuit 

F5 

outdoor current sensor error 

Flash 8 time 

Current sensor fault or no test wire cross it 

F6 

IPM error or Module    control board 
error 

Red and flash 

Communication not good or IPM module fault

 

F7 

compressor fail to start up 

Red and flash 

Compressor cannot start properly   

F8 

outdoor over current 

Red and flash 

Compressor current is too high 

F9 

Discharge sensor error 

Flash 7 time 

Temp sensor open circuit or short circuit 

FA 

Outdoor module overheat, over 
current 

Flash 5 time 

IPM module temp too high or compressor current too 
high 

FB 
/E8

 

outdoor coil over heat 

Flash 15 time 

Outdoor heat exchange not good 

 

P1 

high pressure protection 

Flash 2 time 

1.refrigerant volume too much 2.throtting part error, 3. High 
pressure switch error 

P2 

low pressure protection 

Flash 9 time 

1.refrigerant volume too little 2.throtting part error, 3. low 
pressure switch error 

P3 

compressor discharge air over heat 
protection 

Flash 10 time 

1.Refrigerant too little,    2.throtting part error 

P4 

over current protection 

Flash 11 time 

1.refrigerant volume too much 2.throtting part error, 3. Current 
sensor error 

P5 

indoor unit water flow error 

  No flash 

1.Water flow volume too small    2. Water flow switch error 

P6 

outdoor water flow error ( For GH) 

Flash 17 time 

1.Water source side waterflow volume too small    2. Water 
source side Water flow switch error

 

P7 

miss phase 

Red and flash 

Power supply error 

P8 

wrong phase 

Red and flash 

  power supply error 

P9 

communication error 

Red and flash 

Communication wire open or PCB error 

 

 

 

4.6 :        System Adjustable Parameter Table 

Press M+▲key on wire controller for 3 seconds, it will show PXX to check and set the data 

Code 

name 

Range 

default 

Remark 

P00 

Auto restart   

after power supply, unit come back to the   

previous working mode before power cut off

 

0

off

1

on 

 

P01 

DHW hot water temp differentia 

2~15

℃,

  minus differentia 

2

 

 

Содержание AH9

Страница 1: ...1 DC INVERTER MONOBLOCK AIR TO WATER HEAT PUMP AND CHILLER User Manual REV WR 2017V8...

Страница 2: ...ed during installation for heat pump air conditioning side to ensure proper water flow 2 Water filter MUST be installed before water go into PLATE HEAT EXCHANGER The water filter need to be cleaned at...

Страница 3: ...s 0 factory setting the auxiliary heater switches on to ensure the heat pump unit works normally The unit is also capable of cooling in the summer The heat pump controller is an intelligent wired syst...

Страница 4: ...is led off to a water drain or a suitable soak away The distance between the unit and the exterior wall must be at least 350 mm The free space above must be at least one meter The unit must not be pl...

Страница 5: ...all installation options When connecting with the AH9 11 16 the total water volume in the heat pump pipe system and buffer tank must be at least 10 liters per KW of output A Space Heating Cooling DHW...

Страница 6: ...Cooling DHW Solar Application 1 Solar Application 2 1 Heat Pump 3 DHW sensor 4 Water filter 5 Ball valve 6 Air discharge valve Tap Water Inlet DHW with solar heating C4 Solar hot water system antifree...

Страница 7: ...pe Connection 28mm pipe is recommended The pipe work must be flushed before the heat pump is connected so that any contaminants do not damage the components parts The heating cooling water inlet and o...

Страница 8: ...with the power supply there is still a risk of damage due to freezing During the installation Anti freeze Ethylene Glycol is strongly recommended If the air temp is ever lower than 0c it must use enou...

Страница 9: ...9 Wiring Diagram 3 Phase 3 4 1 Installation Drawing...

Страница 10: ...ver 30 minutes withdraw AC antifreeze When anti freezing if water temperature reduced to 1 C or lower machine will stop and error code Pd display 3 5 COMMISSIONING 3 5 1 Preparations Before commission...

Страница 11: ...ed from the hot water and venting may be necessary If bubbling sounds can be heard from the heat pump the circulation pump or radiators the entire system will require further venting When the system i...

Страница 12: ...ompressor the auxiliary electric heater E2 will start together with E1 When the heat pump is running AC heating A When the heat pump runs AC heating normally the auxiliary electric heater E2 turns on...

Страница 13: ...H water pump or fan motor 13 DHW 14 Sterilization 15 auto mode 16 room heating 17 cooling 18 service icon 19 lock icon 20 Temp 21 Indicating temp location 22 temp unit 23 Defrost icon 24 anti freeze 2...

Страница 14: ...ization will fail to work In on or standby mode first press key M and for 3 seconds second press key M 15 icon appears then press the or to set sterilization temperature press key to confirm the numbe...

Страница 15: ...y select the setting period press to confirm Hour number flash as below 2 Press up and down key to select number of hour press to confirm After confirmation minute number flash press up and down key t...

Страница 16: ...eed 4 4 6 Auto mode icon Automatically select heating or cooling mode After you select AUTO mode when ambient temp 15C it run AC cooling mode When ambient temp 25C it run AC cooling mode When ambient...

Страница 17: ...ssor abnormal stop Red and flash compressor stops abnormally F4 outdoor module radiator sensor error Flash 5 time Temp sensor open circuit or short circuit F5 outdoor current sensor error Flash 8 time...

Страница 18: ...y only 0 P24 EEV Temp differential to stop the valve heating 5 10 for factory only 0 P25 EEV temp differential to stop the valve cooling 5 10 for factory only 0 P26 water pump working mode 0 no stop 1...

Страница 19: ...h a beep parameter reset indoor PCB need to power off and on again to make the change valid parameter reset to default 4 functional parameter P14 When parameter valve 1 when unit working with AC heati...

Страница 20: ...2 four way valve 1 on 0 off 23 bypass valve 1 on 0 off 24 1 electrical valve 1 on 0 off 25 2 electrical valve 1 on 0 off 26 3 electrical valve 1 on 0 off 27 1 electrical heater 1 1 on 0 off 28 2 elect...

Страница 21: ...21 5 1 Internal View 5 2 System Drawing AH9 11 16 17S 25S...

Страница 22: ...22 5 3 Dimensions Model 9 W 1090 D 420 H 780 A 440 B 810 16 17S 1280mm for 16 17S 1462mm for 25S...

Страница 23: ...has power in the winter whether the unit is used or not 6 2 Maintenance for Specialist 1 Check the power unit and electrical system 2 Check the water system safety valves and exhaust devices are work...

Страница 24: ...he same time you could set the water temperature lower This will basically charge your home during the day so in the evening the home is warm and the heat pump simply maintains the heat This is not co...

Отзывы: