- 12- 

      When parameter P27= 0, E2 is AC heating control port, When parameter P27 = 1, E2 is 2

nd

 

heat source control port 

d)    DHW Auxiliary Electric Heater E1

 

When parameter P27 = ―1‖,

 When E2 not start, E1 will work as normal DHW assistant 

heater. When E2 start, E1 will be off.  

When P27=‖0‖, the auxiliary electric heater 

E1

 turns on as set out in the conditions below: 

 

Ambient temperature ≤ set value (parameter P09,-20 

 ~ 30 

, default 0 

); 

 

Compressor’s working time ≥ 15 minutes; 

 

DHW water tank temperature 

  setting temperature; 

When  start defrost  mode at DHW mode, E1 will  be on  if DHW  temp<38c. when  DHW 

temp>42c, E1 off. 

When DHW antifreeze, E1 is on, when DH>15C, E1 off. 

When some error cause compressor stop, if DHW required, E1 will be on. 

 

e)      Multifunctional port E2 

          When parameter P27= “1”, E2 

is for 2

nd

 heat source control 

                       

A, if Ambient temperature 

  set value (parameter P28),   

E2 On, heat pump standby. 

                        B, if Ambient temperature ≥ set value (parameter P28, default -15 

), 

  E2 Off, heat pump start working. 
When P27=‖0‖ 

E2 

is for AC auxiliary electric heater. 

E2 turns on as set out in the conditions below: 

 

When the heat pump is running AC heating or DHW but some error happen to stop 
compressor, the auxiliary electric heater E2 will start together with E1. 

 

When the heat pump is running AC heating: 

A, When the heat pump runs AC heating normally, the auxiliary electric heater 

E2

 turns on as 

set out in the conditions below: 

 

Ambient temperature ≤ set value (parameter P10); 

 

Compressor’s working time ≥ 15minutes; 

 

AC water inlet temperature

+3C

 

  target inlet water temperature; 

B, 

When  start  defrost  at  AC  heating  mode,  if  inlet  water  temperature  ≤25 

E2 

turns  on. 

When Ac inlet temp>30c, E2 off. 

C, During AC antifreezing, the auxiliary electric heater 

E2 

turns on. 

D, If inlet or outlet temperature sensor breakdown, the auxiliary electric heater 

E2 

turns on. 

 

f)    Motorized 3 way Valve G2

 

In DHW mode, the motorized 3 way valve is power on.    In any other mode, it is power off.   

 

4.2:        .Operating Mode Principle   

1)

 

Space Cooling Mode   

Temperature setting range is 10-25 ° C, the factory setting is 12 

2)

 

Space Heating Mode   

Temperature setting range is 10-55 ° C, the factory setting is 45

3)

 

Hot Water Mode 

Temperature setting range is 10-60 ° C(50~60c is increased by electric heater), the factory setting 
is 50 

4)

 

Defrost Cycle   

Auto Defrost mode (normal defrosting) 

All    heat pumps are fitted with intelligent defrost controls. A number of parameters are taken into 

account  before  defrost  begins  and  ends.  The  parameters  should  be  set  as  per  factory  settings  or 

Содержание AH9

Страница 1: ...1 DC INVERTER MONOBLOCK AIR TO WATER HEAT PUMP AND CHILLER User Manual REV WR 2017V8...

Страница 2: ...ed during installation for heat pump air conditioning side to ensure proper water flow 2 Water filter MUST be installed before water go into PLATE HEAT EXCHANGER The water filter need to be cleaned at...

Страница 3: ...s 0 factory setting the auxiliary heater switches on to ensure the heat pump unit works normally The unit is also capable of cooling in the summer The heat pump controller is an intelligent wired syst...

Страница 4: ...is led off to a water drain or a suitable soak away The distance between the unit and the exterior wall must be at least 350 mm The free space above must be at least one meter The unit must not be pl...

Страница 5: ...all installation options When connecting with the AH9 11 16 the total water volume in the heat pump pipe system and buffer tank must be at least 10 liters per KW of output A Space Heating Cooling DHW...

Страница 6: ...Cooling DHW Solar Application 1 Solar Application 2 1 Heat Pump 3 DHW sensor 4 Water filter 5 Ball valve 6 Air discharge valve Tap Water Inlet DHW with solar heating C4 Solar hot water system antifree...

Страница 7: ...pe Connection 28mm pipe is recommended The pipe work must be flushed before the heat pump is connected so that any contaminants do not damage the components parts The heating cooling water inlet and o...

Страница 8: ...with the power supply there is still a risk of damage due to freezing During the installation Anti freeze Ethylene Glycol is strongly recommended If the air temp is ever lower than 0c it must use enou...

Страница 9: ...9 Wiring Diagram 3 Phase 3 4 1 Installation Drawing...

Страница 10: ...ver 30 minutes withdraw AC antifreeze When anti freezing if water temperature reduced to 1 C or lower machine will stop and error code Pd display 3 5 COMMISSIONING 3 5 1 Preparations Before commission...

Страница 11: ...ed from the hot water and venting may be necessary If bubbling sounds can be heard from the heat pump the circulation pump or radiators the entire system will require further venting When the system i...

Страница 12: ...ompressor the auxiliary electric heater E2 will start together with E1 When the heat pump is running AC heating A When the heat pump runs AC heating normally the auxiliary electric heater E2 turns on...

Страница 13: ...H water pump or fan motor 13 DHW 14 Sterilization 15 auto mode 16 room heating 17 cooling 18 service icon 19 lock icon 20 Temp 21 Indicating temp location 22 temp unit 23 Defrost icon 24 anti freeze 2...

Страница 14: ...ization will fail to work In on or standby mode first press key M and for 3 seconds second press key M 15 icon appears then press the or to set sterilization temperature press key to confirm the numbe...

Страница 15: ...y select the setting period press to confirm Hour number flash as below 2 Press up and down key to select number of hour press to confirm After confirmation minute number flash press up and down key t...

Страница 16: ...eed 4 4 6 Auto mode icon Automatically select heating or cooling mode After you select AUTO mode when ambient temp 15C it run AC cooling mode When ambient temp 25C it run AC cooling mode When ambient...

Страница 17: ...ssor abnormal stop Red and flash compressor stops abnormally F4 outdoor module radiator sensor error Flash 5 time Temp sensor open circuit or short circuit F5 outdoor current sensor error Flash 8 time...

Страница 18: ...y only 0 P24 EEV Temp differential to stop the valve heating 5 10 for factory only 0 P25 EEV temp differential to stop the valve cooling 5 10 for factory only 0 P26 water pump working mode 0 no stop 1...

Страница 19: ...h a beep parameter reset indoor PCB need to power off and on again to make the change valid parameter reset to default 4 functional parameter P14 When parameter valve 1 when unit working with AC heati...

Страница 20: ...2 four way valve 1 on 0 off 23 bypass valve 1 on 0 off 24 1 electrical valve 1 on 0 off 25 2 electrical valve 1 on 0 off 26 3 electrical valve 1 on 0 off 27 1 electrical heater 1 1 on 0 off 28 2 elect...

Страница 21: ...21 5 1 Internal View 5 2 System Drawing AH9 11 16 17S 25S...

Страница 22: ...22 5 3 Dimensions Model 9 W 1090 D 420 H 780 A 440 B 810 16 17S 1280mm for 16 17S 1462mm for 25S...

Страница 23: ...has power in the winter whether the unit is used or not 6 2 Maintenance for Specialist 1 Check the power unit and electrical system 2 Check the water system safety valves and exhaust devices are work...

Страница 24: ...he same time you could set the water temperature lower This will basically charge your home during the day so in the evening the home is warm and the heat pump simply maintains the heat This is not co...

Отзывы: