manualshive.com logo in svg
background image

                                                                                                                                                   

 

- 19- 

setting on the work site.  

In case reset all the parameters, the below points have to be reset according to 

below table for different model, otherwise the unit can not work properlly. 

 
        Correct Parameter value 

Code 

Meaning 

Range 

9KW   
Correct 
value 

11KW 
Correct 
value 

16KW 
Correct 
value 

P21 

EEV  manual  open  degree 
(heating) /2 

50~240 

180 

200 

180 

P22 

EEV  manual  open  degree 
(cooling)/2 

50~240 

150 

180 

150 

P23  EEV control method 

0-No; 
1-check;2-manual;3-auto 

P24 

EEV Temp differential to 
stop the valve (heating)   

-5~10℃ 

3℃ 

1

 

2

 

P25 

EEV temp differential to 
stop the valve (cooling) 

-5~10℃ 

2℃ 

1

 

4

 

P26  water  pump  working 

methord  

0 (no stop); 1 reach temp 
stop,2 stop for 15 mins 
on 1 min 

2.

 

forced anti bacterial, press M key for 5 seconds. With a beep,    anti bacterial mode works with the setting temp. 

hot water >= anti bacterial setting, exit   

 

3

  parameter reset

press wire controller 

  for 5seconds, with a beep, parameter reset 

indoor PCB need to power 

off and on again to make the change valid. parameter    reset to default

 

4

  functional parameter P14

When parameter valve =1

 

when unit working with AC heating

compare solar water 

tank temp and AC return temp 

 

When solar water tank temp – AC return water temp ≥5℃

electrical three valve G3    ON

when < 2℃

  electrical 3 way 

valve G3 OFF

  When P14=0

G3 is seasonal valve

  AC heating mode

G3 ON

  AC cooling mode

G3 OFF

 

 
 
 
 
 
 
 
 
 
 

4.7 function DIP switch

SW1

after changes, will be valid after power resupply only

 

 

SW1-1 

OFF

water source 

              ON

air source 

SW1-2 

OFF

  AC  heating  control  mode  1

  ON

  AC 

heating control mode 2 

SW1-3 

reserved   

SW1-4 

OFF

  inverter outdoor

          ON

  fix speed outdoor 

SW1-5 

Reserved 

SW1-6 

OFF

  DHW valid

  ON

  DHW not valid 

SW1-7 

OFF

  heating valid 

          ON

    heating not valid 

SW1-8 

OFF

  cooling valid

          ON

  cooling not valid 

 
 

4

8      (Only checkable parameter list) 

          press wire controller 

M +

 keys for 3S

it will show Cx    to check the above parameter 

No 

  name 

Range / meaning 

remark 

00 

out pipe temp 

-30~97

 

 

01 

compressor discharge temp 

-30~128

℃                     

 

 

02 

ambient temp 

-30~97℃ 

Calculation 

SW1 

Содержание AH9

Страница 1: ...1 DC INVERTER MONOBLOCK AIR TO WATER HEAT PUMP AND CHILLER User Manual REV WR 2017V8...

Страница 2: ...ed during installation for heat pump air conditioning side to ensure proper water flow 2 Water filter MUST be installed before water go into PLATE HEAT EXCHANGER The water filter need to be cleaned at...

Страница 3: ...s 0 factory setting the auxiliary heater switches on to ensure the heat pump unit works normally The unit is also capable of cooling in the summer The heat pump controller is an intelligent wired syst...

Страница 4: ...is led off to a water drain or a suitable soak away The distance between the unit and the exterior wall must be at least 350 mm The free space above must be at least one meter The unit must not be pl...

Страница 5: ...all installation options When connecting with the AH9 11 16 the total water volume in the heat pump pipe system and buffer tank must be at least 10 liters per KW of output A Space Heating Cooling DHW...

Страница 6: ...Cooling DHW Solar Application 1 Solar Application 2 1 Heat Pump 3 DHW sensor 4 Water filter 5 Ball valve 6 Air discharge valve Tap Water Inlet DHW with solar heating C4 Solar hot water system antifree...

Страница 7: ...pe Connection 28mm pipe is recommended The pipe work must be flushed before the heat pump is connected so that any contaminants do not damage the components parts The heating cooling water inlet and o...

Страница 8: ...with the power supply there is still a risk of damage due to freezing During the installation Anti freeze Ethylene Glycol is strongly recommended If the air temp is ever lower than 0c it must use enou...

Страница 9: ...9 Wiring Diagram 3 Phase 3 4 1 Installation Drawing...

Страница 10: ...ver 30 minutes withdraw AC antifreeze When anti freezing if water temperature reduced to 1 C or lower machine will stop and error code Pd display 3 5 COMMISSIONING 3 5 1 Preparations Before commission...

Страница 11: ...ed from the hot water and venting may be necessary If bubbling sounds can be heard from the heat pump the circulation pump or radiators the entire system will require further venting When the system i...

Страница 12: ...ompressor the auxiliary electric heater E2 will start together with E1 When the heat pump is running AC heating A When the heat pump runs AC heating normally the auxiliary electric heater E2 turns on...

Страница 13: ...H water pump or fan motor 13 DHW 14 Sterilization 15 auto mode 16 room heating 17 cooling 18 service icon 19 lock icon 20 Temp 21 Indicating temp location 22 temp unit 23 Defrost icon 24 anti freeze 2...

Страница 14: ...ization will fail to work In on or standby mode first press key M and for 3 seconds second press key M 15 icon appears then press the or to set sterilization temperature press key to confirm the numbe...

Страница 15: ...y select the setting period press to confirm Hour number flash as below 2 Press up and down key to select number of hour press to confirm After confirmation minute number flash press up and down key t...

Страница 16: ...eed 4 4 6 Auto mode icon Automatically select heating or cooling mode After you select AUTO mode when ambient temp 15C it run AC cooling mode When ambient temp 25C it run AC cooling mode When ambient...

Страница 17: ...ssor abnormal stop Red and flash compressor stops abnormally F4 outdoor module radiator sensor error Flash 5 time Temp sensor open circuit or short circuit F5 outdoor current sensor error Flash 8 time...

Страница 18: ...y only 0 P24 EEV Temp differential to stop the valve heating 5 10 for factory only 0 P25 EEV temp differential to stop the valve cooling 5 10 for factory only 0 P26 water pump working mode 0 no stop 1...

Страница 19: ...h a beep parameter reset indoor PCB need to power off and on again to make the change valid parameter reset to default 4 functional parameter P14 When parameter valve 1 when unit working with AC heati...

Страница 20: ...2 four way valve 1 on 0 off 23 bypass valve 1 on 0 off 24 1 electrical valve 1 on 0 off 25 2 electrical valve 1 on 0 off 26 3 electrical valve 1 on 0 off 27 1 electrical heater 1 1 on 0 off 28 2 elect...

Страница 21: ...21 5 1 Internal View 5 2 System Drawing AH9 11 16 17S 25S...

Страница 22: ...22 5 3 Dimensions Model 9 W 1090 D 420 H 780 A 440 B 810 16 17S 1280mm for 16 17S 1462mm for 25S...

Страница 23: ...has power in the winter whether the unit is used or not 6 2 Maintenance for Specialist 1 Check the power unit and electrical system 2 Check the water system safety valves and exhaust devices are work...

Страница 24: ...he same time you could set the water temperature lower This will basically charge your home during the day so in the evening the home is warm and the heat pump simply maintains the heat This is not co...

Отзывы: