17
8. Docking of the Drive Unit to the Tank and Biocontainer
8.1. Drive configuration
The drive unit can be used in one of two configurations: standard or extended. The configurations
can be switched following the procedure described in Section 11.3.1.
Each configuration allows connection of the unit to different tank sizes using a universal latch as
shown in Figure 18. Positions 1 and 2 are in standard configuration; positions 3 and 4 are in
extended configuration.
The table below shows the different latch positions for each tank size.
Marks on the frame at each latch show proper positioning of the latch in combination with the
round plastic tanks
Figure 17: Different latch positions for drive unit
Table 4: Latch positions/configuration cubical tanks
Cubical Tank Latch Positions
Volume
Position
Stamp on frame
Configuration
50 L
2
(23) 15
standard
100 L
2
(23) 15
standard
200 L
2
(23) 15
standard
400 L
2
(23) 15
standard
650 L
4
(23) 15
extended
1000 L
4
(23) 15
extended
1500 L
4
(23) 15
extended
2000 L
4
(23) 15
extended
3000 L
4
(23) 15
extended
Position 1
Position 2
Position 3
Position 4
Содержание Allegro MMG403
Страница 39: ...39 Figure 38 Left Standard configuration Right Extended configuration ...
Страница 47: ...47 15 Electrical Diagram Figure 48 Electrical diagram control box ...
Страница 48: ...48 Figure 49 Electrical diagram drive box ...
Страница 50: ...50 16 CE Certificate ...
Страница 53: ...53 ...