GeneraL ruLes to ensure Perfect
oPeratIon of tHe fIrePLace
Figures 5.1 and 5.2 show the table data referring to the
uNI 10683/98 provisions relative to the distances and
positioning of the chimney tops.
unI 10683/98 - cHImney toPs, dIstances and PosItIonInG
Roof
slant
Distance between
the ridge cap and chimney
Minimum chimney height
0,50 m beyond the ridge cap
1,00 m from the roof
0,50 m beyond the ridge cap
1,30 m from the roof
0,50 m beyond the ridge cap
2,00 m from the roof
0,50 m beyond the ridge cap
2,60 m from the roof
less than 1,85 m
greater than 1,85 m
less than 1,50 m
greater than 1,50 m
less than 1,30 m
greater than 1,30 m
less than 1,20 m
greater than 1,20 m
L
= distance shorter than 5 m.
L1
= distance longer than 5 m
K
= 0,50 m
5
aLLGemeIne BestImmunGen fÜr eInen
eInWandfreIen BetrIeB des KamInofens
In den Abbildungen 5.1 und 5.2 werden die daten
der Tabelle der Bestimmungen laut uNI 10683/98
bezüglich der Abstände und der Anordnung der
Schornsteine dargestellt.
unI 10683/98 - scHornsteIne, aBstÄnde und anordnunG
Neigung des
Dachs
Abstand zweischen
Dachfirst und Kamin
Mindesthöhe des Kamins
0,50 m über den Dackfirst hinaus
1,00 m vom Dach
0,50 m über den Dackfirst hinaus
1,30 m vom Dach
0,50 m über den Dackfirst hinaus
2,00 m vom Dach
0,50 m über den Dackfirst hinaus
2,60 m vom Dach
weniger als 1,85 m
Höher als 1,85 m
weniger als 1,50 m
Höher als 1,50 m
weniger als 1,30 m
Höher als 1,30 m
weniger als 1,20 m
Höher als 1,20 m
L
= Abstand unter 5 m.
L1
= Abstand über 5 m
K
= 0,50 m