Failure indication
Internal function failure will be indicated by activating both alarm relays at
the same time, or indicated as defined in the NAMUR NE43.
Internal failures includes:
Sensor reading out of range.
Sensor reading CRC error.
Unstable Sensor reading.
NAMUR NE43 is a German fault detection standard for 4-20mA analogue
signals. It allows the user to know if there is a fault within the instrument,
by sending analogue signal below 4mA and/or above 20mA. In accordance
with NAMUR NE43, the failure is indicated by:
Fault indicated by analogue output =<2,0 mA