ROGOWSKI COIL SENSOR
1.
Disconnect power to the BGS16 if possible.
If it is not possible to disconnect power, always treat the coil leads as
though they carry line voltages. Work on live panels must only be
performed by qualified personnel.
2.
Disconnect the Rogowski coil to be replaced using the quick disconnect attached to
the cable.
3.
Open the Rogowski coil by pinching the closing unit on the side of the connector
and remove from the conductor.
4.
Position the new coil on the conductor such that the
arrow on the connector faces
toward the load and away from the source
.
5.
Close the Rogowski coil and ensure the closing unit has clicked into place.
6.
Connect the coil cable to the corresponding CT lead using the quick connectors.
7.
Update any panel maps or third-party software interfaces as appropriate.
The arrow on the coil
connector faces toward
the load and away from
the source.