SECTION 4
OPERATION
64
4.6.3.3 UPC STATUS (continued)
BAUD:
300, 1200, 2400, 4800, 9600, 19200, 38400
. This is the serial port baud rate. The
factory default value is 19200.
PARITY:
NONE, ODD or EVEN
. The default serial port parity value is NONE.
LAST BYTE=
Same as LAST DATA BYTE, above.
TRANSFORMER RATIO
(Output Transformer)
:
This value MUST match the ratio of the output transformer
that is presently installed. See (
) CONFIGURE TRANSFORMER RATIO.
PAs=
1
,
2
, or
3
. This is the number of power amplifiers in the Power Source. See
) CONFIGURE MISCELLANEOUS SETTINGS.
AMPS:VOLTS RATIO
This sets the ratio of current to voltage for the UPC metering signals. See (
CONFIGURE AMPS TO VOLTS RATIO.
PRI/SEC:
PRI
mary or
SEC
ondary. This is the current transformer location relative to an
output transformer. See (
) CONFIGURE MISCELLANEOUS SETTINGS.
EOS=
CR/LF, LF
(0Ahex, 10dec)
or CR
(0Dhex, 13dec). The factory default Serial port
End-Of-String character(s) value is CR/LF. Use the +/- key to select this value.
4.6.3.4 POWER SOURCE STATUS
POWER SOURCE STATUS indicates the state of internal control signals between the UPC and the Power
Source circuits. See (
) INPUT CONTROL for a description of these
signals. This display is only used for technical diagnostics.
The POWER SOURCE STATUS menu is accessed from the General Setup menu (
fn
,
3
,4).
POWER SOURCE STATUS:
3PH 1PH CONNECTOR XFMR
CMD FALSE FALSE FALSE FALSE
CONF FALSE FALSE FALSE FALSE
CMD
:
Command signals sent from the UPC to the Power Source.
CONF
:
Confirmation signals sent from the Power Source to the UPC.
Pressing the
+/-
key toggles the Connector CMD signal state.
4.6.3.5 RANGE CONTROL
Some power source models support Range Control to improve efficiency by matching the internal power
supply to the output voltage requirement. The UPC displays the Range Control parameters even when it is
not supported by the attached power source. In this case the following screens would have no effect.
The RANGE CONTROL SETUP menu is accessed from the General Setup menu (
fn
,
3
,
5
).
RANGE CONTROL MODE: MANUAL
SELECT OUTPUT RANGE: 1
Содержание UPC-32
Страница 1: ...UPC 32 UPC 12 PROGRAMMABLE CONTROLLERS FIRMWARE V5 22 AND LATER OPERATION MANUAL PACIFIC POWER SOURCE...
Страница 2: ......
Страница 15: ...SECTION 1 GENERAL 5 PACIFIC Figure 1 3a SCU UPC 32 Figure 1 3b UPC 32 Figure 1 3c UPC 12...
Страница 40: ...SECTION 4 OPERATION 30 PA CIFIC FIGURE 4 1 POWER SOURCE FRONT PANEL...
Страница 127: ...NOTES 117 NOTES...
Страница 128: ...MODIFICATIONS 118 MODIFICATIONS MODIFICATIONS This section is reserved for any modifications that may be made...