SECTION 8
CALIBRATION
102
8.3
EXTERNALLY REFERENCED CALIBRATION (continued)
To calibrate the UPC metering:
NOTE:
It is recommended that the existing calibration factors (kFactors) should be recorded for
reference (fn,4,3), and set to default (1.000) value (fn,4,1) before starting calibration. That allows
restoration to the existing condition if a problem is encountered.
1.
Apply power to the power source and UPC.
2.
Press
fn
to invoke the SETUP menu.
3.
Press
4
to select the 'CALIBRATION' menu.
CALIBRATION MENU:
1 RESET ALL KFACTORS
2 EXTERNALLY REFERENCED METER CALIBRATION
3 KFACTOR DISPLAY
4.
Press
2
to select EXTERNALLY REFERENCED METER CALIBRATION
Press
EDIT
to allow voltages to be entered.
Press
ENTER
to advance the cursor.
Ф
INT.V-SENSE EXT.V-SENSE | I1 0.00
A 0.000 0.000 | Ia 0.00
B 0.000 0.000 | Ib 0.00
C 0.000 0.000 | Ic 0.00
5.
Enter the measurements taken with external test equipment (voltmeter, ammeter) for each
parameter shown on the UPC display. All measurements taken are to be AC RMS (True
RMS metering is absolutely necessary), Line to Neutral only for voltages.
6.
Upon completion, press
EXECUTE
.
NOTE:
When calibrating EXT.V-SENSE, the External Sense terminals at the rear of the power source must
be connected to the output voltage and the output must be enabled.
The UPC has one current metering circuit for FORM 1, and another for FORM 2 and FORM 3. In order to
fully calibrate all current meters for all power forms, this procedure must be performed twice.
UPC-12
a. Operate the power source in FORM 1 to calibrate
I1
(single phase).
b. Operate the power source in FORM 2 to calibrate
Ia
and
Ib
(single/split phase).
UPC-32
a. Operate the power source in FORM 1 to calibrate
I1
(single phase).
b. Operate the power source in FORM 3 to calibrate
Ia, Ib
and
Ic
(three phase).
Only existent phases need to have values entered. If a phase is not available as in the case of a 1 or 2
phase power source, the phase C parameters should be set to 0. Entering 0 for a parameter causes the
correction factor (kFactor) for that parameter to be set to the system default value, 1.0000.
NOTE:
Only
I1
or
Ia, Ib
and
Ic
can be entered depending upon the power form currently in use.
NOTE:
Voltages are to be entered as AC RMS,
LINE TO NEUTRAL only for voltages
.
Currents are to be entered as AC RMS.
Each time a non-zero value is entered, the UPC measures the output signal for that parameter and
compares it against the entered external meter calibration value. A new calibration factor (k factor) is then
calculated and used to correct the meter display for that value.
If a value for a parameter is not keyed in, the existing calibration factor will remain in memory and will not be
re-calculated. The kfactors are stored in memory until the memory is lost or cleared.
Содержание UPC-32
Страница 1: ...UPC 32 UPC 12 PROGRAMMABLE CONTROLLERS FIRMWARE V5 22 AND LATER OPERATION MANUAL PACIFIC POWER SOURCE...
Страница 2: ......
Страница 15: ...SECTION 1 GENERAL 5 PACIFIC Figure 1 3a SCU UPC 32 Figure 1 3b UPC 32 Figure 1 3c UPC 12...
Страница 40: ...SECTION 4 OPERATION 30 PA CIFIC FIGURE 4 1 POWER SOURCE FRONT PANEL...
Страница 127: ...NOTES 117 NOTES...
Страница 128: ...MODIFICATIONS 118 MODIFICATIONS MODIFICATIONS This section is reserved for any modifications that may be made...