10 FUSION_D1 081112-20
Canada Only
Floor Protector
The stove may be installed on a combustible fl oor provided
noncombustible ember protection is used.
This protection must extend as follows:
In Canada: 18" (457 mm) on the fi ring side and 8" (203 mm)
to the other sides. See Figure #4, below.
Combustion Air
Intake or combustion air can be supplied to the stove in one of
two ways. Consult your local building code or CAN/CSA-B365,
Installation Code for Solid-Fuel-Burning Appliances and Equip-
ment before proceeding.
1.
Outside air supply
- (Necessary for mobile home
installation, optional for residential installation.) Outside
air may be drawn from either underneath the stove or from
behind.
To draw outside air through the fl oor, leave the 4" knockout
or cover plate in place in the rear of the stove.
Cut or drill a 4" diameter hole in the fl oor anywhere inside
the perimeter of the pedestal. Cover the hole with a 4" x
4" (100 mm x 100 mm) rodent screen and staple/nail in
place.
This hole must get its air from a
ventilated
crawl space
or be extended with duct to the outdoors (see Figure #3,
Page 7). The use of outside combustion air for residential
installation requires the unit to be secured to the structure
to prevent dislodging of the air duct. Outside air may also
be ducted from outside through the 4" diameter hole in
the rear of the pedestal enclosure if you remove the cover
plate(Fig #6).
Note:
This unit is not designed to be operated with the fi ring
door open. In addition to the obvious hazard of sparks
landing on combustibles, an open fi re door will cause the
heater to draw air from the living space and possibly cause
suffocation.
2.
Room air supply
- Remove the 4" cover from the rear of
the pedestal enclosure. The stove will now draw its air
from the room through this opening and into the fi rebox
intake(Fig.#6).
Note:
The living space around the heater must be well
ventilated with good air circulation. Anything that may cause
a negative pressure can cause gases or fumes to be pulled
into the living area. During extremely cold weather, and
especially when burning at very slow rates, the upper parts
of the exposed chimney may ice up, partially blocking the
fl ue gases. If blockage occurs, fl ue gases may enter living
space.
U.S.A. Only
Non-combustible
fl oor protector
FIG. #4
FIG. #5
In USA: 16" (406 mm) to the front and 8" (203 mm) to the sides
of the fuel loading door opening. See Figure #5, below. This
protection is also required under the chimney connector and
2" (51 mm) beyond each side.
Minimum Width - 39 1/4"
Minimum Overall Depth - 51 5/16"
Non-combustible
fl oor protector
Minimum Width - 35"
Minimum Overall Depth - 41 5/16"
8" [203mm]
18" [457mm]
8" [203mm]
8" [203mm]
8" [203mm]
16" [406mm]
8" [203mm]
FIG. #6
Содержание Fusion
Страница 17: ...FUSION_D1 081112 20 17 ...
Страница 18: ...18 FUSION_D1 081112 20 ...