Pacific energy FP30 LE Скачать руководство пользователя страница 45

 Rating Label 

• 

•  LE SYSTÈME DE CHEMINÉE DOIT ÊTRE HOMOLOGUÉ COMME SUIT : AU CANADA - CHEMINÉE HOMOLOGUÉE ULC-S-629, 

LE SYSTÈME DE CHEMINÉE DOIT ÊTRE HOMOLOGUÉ COMME SUIT : AU CANADA - CHEMINÉE HOMOLOGUÉE ULC-S-629,  

•  INSTALLEZ ET UTILISEZ SELON LES INSTRUCTIONS D’INSTALLATION ET D’UTILISATION FOURNIES AVEC LE FOYER.

•  LES PARTIES DU FOYER INCORPORANT DES CONDUITS CHAUDS OU FROIDS DOIVENT ÊTRE ENCHÂSSÉES, CONFORMÉMENT AUX IN-

STRUCTIONS D’INSTALLATION ET D’UTILISATION FOURNIES AVEC LE FOYER.

•  CONTACTEZ LES AGENTS LOCAUX DU CODE DU BÂTIMENT OU DU SERVICE-INCENDIE POUR LES RESTRICTIONS, PERMIS D’INSTALLATION 

ET EXIGENCES D’INSPECTION DANS VOTRE RÉGION.

•  NE RACCORDEZ PAS CE FOYER À UN CONDUIT DE CHEMINÉE DESSERVANT UN AUTRE APPAREIL.

•  NE PAS OBSTRUER PAS LES OUVERTURES DEVANT LE FOYER, NI RESTREINDRE L’ALIMENTATION D’AIR NÉCESSAIRE POUR LE FONC-

TIONNEMENT NORMAL DU FOYER, TEL QUE SPÉCIFIÉ DANS LES INSTRUCTIONS D’INSTALLATION ET D’UTILISATION FOURNIES AVEC 

L’APPAREIL. LA PROVISION INADEQUATE D’AIR POUR COMBUSTION, MAI DE VENTILATION ET DILUTION A POUR RESULTAT L’OPERATION 

DANGEREUSE DE CECI ET AUTRES APPAREILS.

•   VOIR LE CODE DU BÂTIMENT LOCAL ET LES INSTRUCTIONS DU FABRICANT, POUR LES PRÉCAUTIONS EXIGÉES LORSQU’UNE CHEMINÉE 

TRAVERSE UN MUR OU PLAFOND EN MATÉRIAUX COMBUSTIBLES.

•  REMPLACEZ LA VITRE SEULEMENT PAR UNE VITRE EN CÉRAMIQUE. •  LA SOUFFLERIE CLASSEMENT ELECTRIQUE 115V, 60 Hz, 1.1AMP

•  CETTE CHEMINEE n’A pas ETE ESSAYEE AVEC UN UNVENTED JOURNAL DE GAZ A REGLE. POUR REDUIRE LE RISQUE DE FEU OU BLESS-

URE, LE PAS INSTALLE UN UNVENTED JOURNAL DE GAZ A REGLE DANS CHEMINEE. 

•   UTILISEZ SEULEMENT AVEC LA PORTE DE CHARGEMENT FERMÉE. NE L’OUVREZ QUE POUR ALIMENTER LE FEU.

•  CE FOYER PEUT ÊTRE INSTALLÉ DANS UNE MAISON PRÉFABRIQUÉE. UTILISER DU BOIS SOLIDE SEULEMENT.

•  POUR COMBUSTIBLE SOLIDE SEULEMENT.

•   COMPOSANTS OPTIONNELS: KIT DE CONDUITS DE DISTRIBUTION DE CHALEUR (PIÈCE no WODC.RHKA).

•   UTILISEZ LES COMPOSANTS SPÉCIFIÉS DANS LES INSTRUCTIONS D’INSTALLATION DE PACIFIC ENERGY.

MODEL/ MODÈLE:  

FP30 LE          FP30AR LE     

LISTED FACTORY BUILT FIREPLACE. 

Also for use in Mobile Homes

CERTIFIED TO / CERTIFIÉ POUR; 

ULC S610 AND UL 127 for CANADA AND U.S.A.

• •    ALSO FOR USE IN MANUFACTURED HOMES WITH SOLID WOOD FUEL ONLY 

•  INSTALL AND USE IN ACCORDANCE WITH THE INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THE APPLIANCE

•  AREAS OF THE FIREPLACE INCORPORATING WARM OR COLD AIR DUCTS SHALL BE ENCLOSED IN ACCORDANCE WITH THE INSTALLA-

TION AND OPERATING INSTRUCTIONS SUPPLIED WITH THE APPLIANCE.  

•  CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS, INSTALLATION PERMIT AND INSPECTION IN YOUR AREA. 

•  DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE 

•  DO NOT OBSTRUCT THE OPENINGS IN FRONT OF THE FIREPLACE OR OTHERWISE RESTRICT SUPPLY AIR NECESSARY FOR NORMAL FIRE-

PLACE OPERATION AS SPECIFIED IN INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THE APPLIANCE. INADEQUATE AIR 

SUPPLY FOR COMBUSTION, VENTILATION AND DILUTION MAY RESULT IN DANGEROUS OPERATION OF THIS AND OTHER APPLIANCES.

•  CHIMNEY SYSTEM MUST BE LISTED TO: ULC S-629 IN CANADA / UL-103 HT IN USA    - 

ULC S-629 IN CANADA / UL-103 HT IN USA    - SEE LOCAL BUILDING CODE AND MANUFACTURER'S 

INSTRUCTIONS FOR PRECAUTIONS REQUIRED WHEN PASSING A CHIMNEY THROUGH A COMBUSTIBLE WALL OR CEILING.    

•  OPTIONAL COMPONENTS: REMOTE HEAT KIT PART# WODC.RHKA. 

•  USE SOLID WOOD FUEL ONLY. OPERATE ONLY WITH FEED DOOR CLOSED.  OPEN TO FEED FIRE ONLY.

•  BLOWER ELECTRICAL RATING 115V, 60HZ, 1.1AMP   • REPLACE GLASS ONLY WITH 5mm CERAMIC GLASS.

•  DO NOT USE OR INSTALL COMPONENTS OR PRODUCTS NOT SPECIFIED IN PACIFIC ENERGY INSTALLATION INSTRUCTIONS. 

•  DO NOT USE A FIREPLACE INSERT OR OTHER PRODUCTS NOT SPECIFIED FOR USE WITH THIS PRODUCT.

•  THIS FIREPLACE HAS NOT BEEN TESTED WITH AN UNVENTED GAS LOG SET. TO REDUCE RISK OF FIRE OR INJURY, DO NOT INSTALL AN 

UNVENTED GAS LOG SET INTO FIREPLACE.  

•  THIS WOOD HEATER NEEDS PERIODIC INSPECTION AND REPAIR FOR PROPER OPERATION. 

•        - CONSULT THE OWNER’S MANUAL FOR FURTHER INFORMATION.

•  IT IS AGAINST FEDERAL REGULATIONS TO OPERATE THIS WOOD HEATER IN A MANNER INCONSISTANT WITH THE OPERATING 

INSTRUCTIONS IN THE OWNER’S MANUAL.

DO NOT REMOVE THIS LABEL/ NE RETIREZ PAS CETTE ÉTIQUETTE

MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS/ DÉGAGEMENTS MINIMUMS AUX MATÉRIAUX COMBUSTIBLES

ETL#4001507

MANUFACTURED BY/ FABRIQUÉ PAR :

PACIFIC ENERGY FIREPLACE PRODUCTS LTD.

2975 ALLENBY RD., DUNCAN, BC  V9L 6V8

MADE IN CANADA 

/ FABRIQUÉ AU CANADA

040523

100004188

            MANTEL HEIGHT MUST  BE MEASURED FROM THE BASE OF THE UNIT AS FOLLOWS: 51”(1.3m) FOR A 4”(102mm) DEEP MANTEL UP TO 

55”(1.4m) FOR A 12”(305mm) DEEP MANTEL. SEE THE INSTALLATION INSTRUCTIONS FOR GRADUATED MANTEL HEIGHTS MEASURMENTS 

FOR DEPTHS BETWEEN 4”(102mm) AND 12”(305mm).// LA HAUTEUR DU MANTEAU, MESURÉE À PARTIR DE LA BASE DE L’APPAREIL, DOIT 

AVOIR : 51 po (1295 mm) POUR UN MANTEAU DE 4 po (102 mm) DE PROFONDEUR, ET 55 po (1397 mm) POUR UN MANTEAU DE 12 po (305 mm) 

DE PROFONDEUR.  POUR LES PROFONDEURS DE MANTEAU COMPRISES ENTRE 4 po (102 mm) ET 12 po (305 mm), VOIR LES INSTRUCTIONS 

D’INSTALLATION ET D’UTILISATION (TABLEAU GRADUEL DES DIMENSIONS DE MANTEAUX).

***

1.7

g/hr.

Refer to Intertek’s Directory of Building Products for detailed information

DATE OF MANUFACTURE

CLEARANCES TO SIDE AND BACK STANDOFFS/ DÉGAGEMENTS                     

     

0 in. / 0 mm

A. CORNER TO SIDEWALL/ COIN AU MUR LAT. 

                                        

     5 3/8in. / 137mm

B. CEILING TO UNIT/ DU PLAFOND AU FOYER
NON-COMBUSTIBLES ONLY IN THE SPACE ABOVE UNIT TO CEILING, NOT INCLUDING 
APPROVED FRAMING / NON-COMBUSTIBLES SEULEMENT AU-DESSUS FOYER À PLAFOND                                                               
C. BASE OF UNIT TO MANTEL/ BASE DE L’UNITÉ AU MANTEAU  

 

37 in. /940mm 

D. EMBER PROTECTION FROM FRONT OF UNIT/ 
  PROTECTEUR de PLANCHER À L’AVANT DU FOYER                      

          18 in. / 457 mm

F.  EMBER PROTECTION TO SIDE OF UNIT/ 
  PROTECTEUR de PLANCHER AU CÔTÉ DU FOYER                                                                            8 in. /203 mm

IN USA: Type 1 floor protector - approved to UL1618 - Minimum 20GA steel  

***

U.S. ENVIRONMENTAL PROTECTION AGENCY 

Certified to comply with 2020 particulate 

emission standards, 

using Cordwood. 

Tested to ASTM 3053

B

A

C

D

CAN.

U.S.A.

E

E

B

45

100004186_040523-48

FP30 LE

Содержание FP30 LE

Страница 1: ...t version of this manual SAFETY NOTICE If this Fireplace is not properly installed a house fire may result For your safety follow the installation instructions Contact local building or fire officials...

Страница 2: ...n Air 22 Installation 22 Convection Blower Wiring 23 Option Remote Heat Duct Kit Installation 24 Parts 24 Ducting Options 25 Duct Installation 26 Remote Heat Kit Wiring 28 Chase Air Inlets 29 Finshing...

Страница 3: ...let setting is affected by variables such as type of wood outside temperature chimney size and weather conditions With practice you will become proficient in operating your heater and will obtain the...

Страница 4: ...is at the inside front of the firebox 4 If glass becomes darkened through slow burning or poor wood it can be cleaned with fireplace glass cleaner when the fireplace is cold Never scrape with an objec...

Страница 5: ...clearances or within the space required for fuel loading and ash removal Keep the area around the heater clean and free of loose combustibles furniture newspa pers etc 9 Instruct all members of your...

Страница 6: ...any of the damage listed above Continuing to operate your fireplace with broken parts may accelerate damage to other parts and may void your warranty Ash Removal Caution Ashes are to be removed only...

Страница 7: ...BAFFLE ALWAYS COVER THE TOP OF THE BAFFLE AIR TUBE LOCATED IN THE REAR OF THE FIREBOX THIS PREVENTS DEBRIS FALLING DOWN THE TUBE FAILURE TO DO SO WILL RESULT IN POOR OPERATION AND POSSIBLE DAMAGE TO F...

Страница 8: ...control open for long period of time 3 Regular inspections and cleaning In the event of a Chimney Fire Chimney fires are dangerous Temperatures inside the chimney can exceed 2000 F 1093 C This causes...

Страница 9: ...N Hot while in operation Keep children clothing and furniture away Contact may cause skin burns Your PACIFIC ENERGY wood heater is designed for many years of trouble free operation Over firing the app...

Страница 10: ...and should be noted for future burns 2 To refuel adjust air control to High position all the way to the left and give the fire time to brighten Open the door slowly this will prevent backpuffing or fl...

Страница 11: ...e up through the chimney The amount of draft in your chimney depends on the length of the chimney local geography nearby obstructions and other factors Too much draft may cause excessive temperatures...

Страница 12: ...wet Use dry wood 2 Fire too small Build a larger fire 3 Draft too low Chimney plugged or restricted inspect and clean Won t Burn Overnight 1 Air control is set too high Set control lower 2 Not enough...

Страница 13: ...e 3 Access panel bolts Screws Figure 4 Thermoswitch bracket and access panel screws 3 Loosen the two screws securing the thermo switch bracket and slide the bracket back and set aside to clear the ope...

Страница 14: ...ng the blower mounting bracket 7 Gently lift the bracket and slide the blower towards the front of the fireplace 8 Lift the blower up and out of the fireplace through he access openings Terminal block...

Страница 15: ...n into a factory built fireplace Wind direction and magnitude can play a factor in the chimney performance Therefore the chimney out let position is important when locating the fireplace We recommend...

Страница 16: ...to the ceiling 84 2 13 m Minimum chimney height from the base of the Fireplace to below the chimney rain cap 15 4 57 m Recommended maximum chimney height at sea level from top of fireplace to rain cap...

Страница 17: ...rds in the area above this fireplace Do not build or place anything inside this Minimum chase area Do Not insulate the front portion of the chase above the unit The Steel Stud framing kit must be used...

Страница 18: ...alling the unit into the chase Push the Fireplace into place Casing must be flush with the framing in the front and secure as required by local code Place the Steel Framing Kit on top of the unit with...

Страница 19: ...imney must be supported on lengths over 15 4 5m NOTE Install all components following the chimney manufacturer s installation requirements instructions Consult your chimney supplier for installation a...

Страница 20: ...ck the flashing for leaks Minimum 36 915mm length of Chimney before first elbow Maintain Chimney manufacturer s clearances Maximum 48 1 22m total length of Offset chimney Figure 14 FP Offset Installat...

Страница 21: ...clearances around the chimney for its entire length must be to code as per the National Building Code or NFPA 211 The masonry chimney can only be used for this fireplace and no other appliances Make...

Страница 22: ...chase Cover the hole and install a 20GA wire mesh minimum rodent screen and staple nail in place Provide water protection as required by building code Attach 4 102mm venting not supplied between the...

Страница 23: ...ires located in the terminal strip All electrical connections should be performed by a certified licensed electrician Consult local codes or in the absence of local codes with the current CSA C22 2 Ca...

Страница 24: ...floor spaces WARNING THE CHASE ENCLOSURE MUST HAVE A MINIMUM 30in 194 cm ROOM AIR INLET FOR EACH REMOTE HEAT KIT INSTALLED ON THE FIREPLACE The inlets can be combined but it must be 60in or greater A...

Страница 25: ...length and number of bends To maximize the performance the length and number of bends should be kept to a minimum A 12 305mm from the CEILING or SIDE WALLS B 36 914mm from the FLOOR A A B A A Listed B...

Страница 26: ...s 3 Place the Backflow Damper into the top of the unit Figure 24 Ensure that the flap in the assembly is free to move Flap should be in the normally closed position with the blower off 4 Attach the Du...

Страница 27: ...oved Type B flexible or ridged gas vent pipe vent pipe is not included with this kit between the blower and the fireplace Fasten in place with screws and seal with aluminium foil tape 7 Connect the wi...

Страница 28: ...urrent CSA C22 2 Canadian Electrical Code or in the USA the National Electrical Code ANSI NFPA 70 Latest Edition The Remote Heat Kit blower s electrical rating 120V 60HZ 80 watts For your protection a...

Страница 29: ...eplace and blowers and will not be covered under Warranty Finishing The Chase Facing Edge Stop Figure 30 FP30 Facing Edge stop Chase Air Inlets THE CHASE ENCLOSURE MUST HAVE A MINIMUM 30in 194 cm AIR...

Страница 30: ...to expand and contract behind the wall 60 1 524m 31 785mm 25 5 8 650mm 9 3 8 238mm Minimum 84 2 135m 12 1 2 320mm Cement board only in grey area Figure 31 FP30 Non Comb front panelling Hearth A raised...

Страница 31: ...lf must extend onto the floor and under the hearth extension ember protection as shown in Figure 32 If the unit is raised up then a 2 x 2 angled piece can be used against the non combustible face Embe...

Страница 32: ...the Heat Exchanger s air deflector up a minimum of 16 405mm Finishing Clearances Minimum distance to the Mantel side facing Max 4 deep from the side of the fire place door 10 255mm A Raised Hearth mu...

Страница 33: ...1 32 m 17 432 mm 7 178 mm 52 1 2 1 33 m 8 203 mm 53 1 35 m 18 457 mm 9 229 mm 53 1 2 1 36 m 10 254 mm 54 1 37 19 483 mm 11 279 mm 54 1 2 1 38 m 12 305 mm 55 1 4 m 20 508 mm Combustible Mantel 7 2 13m...

Страница 34: ...Use a total of 9 full size A and 1 cut brick C 2 Next install the rear firebricks 4 full size A bricks as shown 3 Finally install 3 full size bricks A and 1 cut firebrick B on each side as shown A A...

Страница 35: ...m deep combustible mantel 14 355mm B Minimum distance from base of the fireplace to 4 100mm deep combustible mantel 51 3 4 1 315m C Minimum distance from top of the Arch to 12 305mm deep combustible m...

Страница 36: ...m 14 355mm A 51 3 4 1 315m B 5 127mm 52 3 4 1 34m 6 150mm 16 406mm 53 3 4 1 365m 7 178mm 54 3 4 1 391m 8 203mm 18 457mm 55 3 4 1 416m 9 229mm 56 3 4 1 441m 10 254mm 20 508mm 57 3 4 1 467m 11 279mm 58...

Страница 37: ...rge hole in the bracket and into the firebox front flange Do not tighten completely 4 Using 5 8 self drilling screws fasten the Side Bracket to the fireplace front using the holes provided in the brac...

Страница 38: ...g as per the board manufacturers guidelines using the dimensions and the Arch template provided Figure 23 Do not place any vertical joints in the wall board above the unit as this may lead to cracking...

Страница 39: ...e house envelope The air must come from inside the house preferably the room the fireplace is installed in Dimensions to note when installing the non combustible wall board A Non combustible wall boar...

Страница 40: ...the rivets Secure the mount on both ends Using a self drilling screw attach through the holes provided 2 Attach the Upper Grill by screwing three 3 8 self drilling screws through the holes in the Gril...

Страница 41: ...the air control level and place the lever through the slot in the lower grill 3 Lift up slightly on one end of the Ash Shelf for clearance hook the grills corresponding mounting slot over the screw he...

Страница 42: ...ront will not be able to mount on the brackets Raised Hearth If you are installing a raised hearth with this unit it must be made entirely of non combustible materials The maximum height for the heart...

Страница 43: ...ots until it drops slightly engaging the mounting tab locks 3 To lock the Front Assembly in place install the four black 8 Torx screws provided into the holes located behind the Front Assembly In the...

Страница 44: ...p Grill Assembly 5 FP30 RP777106 Lower Grill Assembly 6 FP30 RP777101 Front Assembly 7 FP30 RP777104 Upper Decorative Panel 8 FP30 RP777103 Lower Decorative Panel INCLUDED FASTENERS 1 4 20 type F scre...

Страница 45: ...DEQUATE AIR SUPPLY FOR COMBUSTION VENTILATION AND DILUTION MAY RESULT IN DANGEROUS OPERATION OF THIS AND OTHER APPLIANCES CHIMNEY SYSTEM MUST BE LISTED TO ULC S 629 IN CANADA UL 103 HT IN USA ULC S 62...

Страница 46: ...mbly FP30 Arch 80000805 14 Replacement Baffle Kit 80000396 15 Side Insulation 80001712 16 Baffle Gasket pkg of 10 80000400 17 Baffle Pin 10pcs 80000364 18 Brick Rail Kit Sides 80000185 19 Brick Rail R...

Страница 47: ...1 5 7 10 14 8 9 6 20 1 17 25 16 15 18 21 24 23 13 22 11 2 4 3 26 19 47 100004186_040523 48 FP30 LE...

Страница 48: ...Products LTD Reproduction adaptation or translation without prior written permission is prohibited except as allowed under the copyright laws For technical support please contact your retailer Web sit...

Отзывы: