DO NOT place any facing materials inside the facing edge/stop. This will prevent proper airflow into the
blowers
Only non combustible materials can be used in the area shown below;
• Extending from the outer edge of the door out 10" [255mm],
• Under the door, down to the floor.
• Above the Heat Exchanger's air deflector up a minimum of 16" [405mm].
Finishing Clearances
Minimum distance to the Mantel side facing (Max 4” deep) from the side of the fire-
place door.
10” (255mm)
A Raised Hearth must be completly constructed of non-combustible materials and
can only be 9-3/8" (238mm) from the base of the unit**
10”
[255mm]
16 ”
[405mm]
10”
[255mm]
NO
COMBUSTIBLE
FINISHING MATERIALS
Allowed in this area
9 3/8”
[238mm]
Figure 35: FP30 finishing dimensions.
32
100004186_040523-48
FP30 LE