boiler temperature is 2°C lower than desired boiler temperature the fan will work with

its maximum power [Π100]. Further increase of boiler temperature will cause fan

speed to be reduced gradually to its minimum power [n 40].

Automatic fan speed control [Πr 1]

– it is on, when this parameteris set to „0-10” and

causes automatic fan speed decrease whentemperature of water in the boiler reaches

desired temperature.If this parameter is set to „-”, the fan automatic smooth

speedcontrol is disabled and the fan can work with power set by „Π” parameter.

Setting parameter value in range from 0 to 10 meanstime in minutes of the smooth fan

speed increase from 40% tovalue of „Π” for smooth boiler start.

Fan work time [Πn 5]

– time of turning the fan on for a while, to remove accumulated

gases. Setting the parameter to „-” turns this function off. This function can be active in

WORK mode.

Fan pause time [Πu 6]

– time between fan work periods

4.2. Circulating pump parameters.

Circulating pump launch temperature [P 62]

– temperature of water in the boiler,

which causes start of the circulating pump. Circulating pump works independently

from the control process and is launched additionally in case of boiler overheat.

Circulating pump launch hysteresis [Ph 2]

– this parameter defines what value

should temperature decrease by, below circulating pump launch temperature, to turn

the pump off.

The work mode and pause time of CH pump [Pc 2]

– in STOP mode or when the

room thermostat circuit is not shorted, CO pump is turned on for 30 seconds to move

water in the heating system. This parameter controls the repeat time. Setting this

parameter to „--” turns this function off. In case of some heating systems the pump

should work independently of room thermostat. In such case the parameter should be

set to value „F”.

4.3. Boiler work temperature setting.

Minimal boiler temperature [L 65]

– minimal temperature, which you can set with the

boiler thermostat knob.

Maximum boiler temperature [H 85]

– maximum temperature, which you can set

with the boiler thermostat knob.

Boiler temperature hysteresis [h 2]

– this parameter defines what value should

temperature of water in the boiler decrease by, below temperature set with the

thermostat knob, to turn the pressure fan on.

Содержание RK-2001E2-D

Страница 1: ...OPERATION MANUAL SOLID FUEL FIRED BOILER TEMPERATURE CONTROLLER RK 2001E2 D Version 9A15...

Страница 2: ......

Страница 3: ...placed in measurement hole in the boiler Picture 2 shows diagram of electrical connection of the device WARNING Before plugging the device to the power source check if it is proprerly grounded and if...

Страница 4: ...ler If the controller isn t in service mode the display shows water temperature of the boiler and the last sign on the display defines mode which controller currently is in for example 50 STOP mode 50...

Страница 5: ...olling emergency cooling system 4 output controlling extra devices turning on during work of blow in fan 0 4 1 0 Prod Return to factory defaults outP Central heating pump testing outP out1 out Fan out...

Страница 6: ...in the boiler which causes start of the circulating pump Circulating pump works independently from the control process and is launched additionally in case of boiler overheat Circulating pump launch...

Страница 7: ...o previous mode by pressing STOP button No fuel testing time during fuel firing is finished after the set temperature is achieved No fuel testing time during work mode Fb30 in WORK mode if temperature...

Страница 8: ...set by the producer by choosing Prod option in service mode and pressing OK button After activating this function the device sets each parameter showed in the table to default 4 9 Exiting service mode...

Страница 9: ...d if boiler overheats E 3 error means fault and overheating at the same time Appearing of E 1 error on the display without ability to cancel it by pressing STOP button in spite of temperature below 90...

Страница 10: ...10 Picture 2 RK 2001E2 connection scheme Picture 3 UM 1 module connection scheme...

Страница 11: ...2 The work mode and pause time of CH pump L 65 Minimum boiler temperature H 85 Maximum boiler temperature h 2 Boiler temperature hysteresis A 99 Boiler overheating temperature Fd60 Fuel shortage testi...

Страница 12: ...12...

Страница 13: ...13...

Страница 14: ...14...

Страница 15: ......

Страница 16: ...Producer P W KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl...

Отзывы: