background image

5

Table 1. Service parameter's list

Disp.

Parameter

Min Max Step Factory

default

Π100 Fan max work power or max power when Πr 0-10.

50

100 10%

100

n 40 Minimum fan power.

20

40

10%

40

Πh 2 Fan speed decrease coefficient.

2

10

1

2

Πr 1 Automatic fan speed control and time of fan start.

--, 0

10

1

1

Πn 5 Fan work time.

--, 5

60

1s

5

Πu 6 Fan pause time.

1

99 1min

6

P 62 Central heating pump launch temperature.

30

70

1ºC

62

Ph 2 Central heating pump hysteresis.

1

10

1ºC

2

Pc 2 The work mode and pause time of CH pump.

--, 1 99, F 1min

2

L 65 Minimum boiler temperature.

30

65

1ºC

65

H 85 Maximum boiler temperature.

80

90

1ºC

85

h 2

Boiler temperature hysteresis.

1

10

1ºC

2

A 99 Boiler overheating temperature.

90

99

1ºC

99

Fd60 Fuel shortage testing time with burning.

--, 1 99, 4h 1min

60

Fb30 Fuel shortage testing time in WORK mode and

burning out.

--, 1 99, 4h 1min

30

Ar 0

Work mode of extra output:

0– output turning on extra boiler,

1– alarm output,

2– output controlling mixing valve,

3– output controlling emergency cooling system,

4– output controlling extra devices turning on during

work of blow-in fan.

0

4

1

0

Prod Return to factory defaults.

outP Central heating pump testing.

outP out1

outΠ Fan output testing.

outΠ out2

outr

Additional output testing.

outr out3

End Exit the service mode.

In the table above, the first column represents example display indications, in the next

columns there are: parameter description, minimal amount, maximum amount allowed

to set, step of the parameter during the setup, factory defaults, to which you can return

by choosing [Prod] option.

4.1. Pressure fan work parameters.

Fan power [Π100]

– this value defines power of the fan. When „Πr”parameter is set to

„0-10” this is the maximum power of the fanwhich can be achieved during automatic

fan control.

Minimum fan power [n 40]

– lowest fan power which can be used when automatic

fan speed control is on and when fan speed is gradually increased during boiler start.

Fan speed decrease coefficient [Πh 2]

– this parameter influences the way fan

speed is reduced when boiler tremperature is approaching its desired value. E.g.

setting this parameter to 2 means that when the controller is in WORK mode and

Содержание RK-2001E2-D

Страница 1: ...OPERATION MANUAL SOLID FUEL FIRED BOILER TEMPERATURE CONTROLLER RK 2001E2 D Version 9A15...

Страница 2: ......

Страница 3: ...placed in measurement hole in the boiler Picture 2 shows diagram of electrical connection of the device WARNING Before plugging the device to the power source check if it is proprerly grounded and if...

Страница 4: ...ler If the controller isn t in service mode the display shows water temperature of the boiler and the last sign on the display defines mode which controller currently is in for example 50 STOP mode 50...

Страница 5: ...olling emergency cooling system 4 output controlling extra devices turning on during work of blow in fan 0 4 1 0 Prod Return to factory defaults outP Central heating pump testing outP out1 out Fan out...

Страница 6: ...in the boiler which causes start of the circulating pump Circulating pump works independently from the control process and is launched additionally in case of boiler overheat Circulating pump launch...

Страница 7: ...o previous mode by pressing STOP button No fuel testing time during fuel firing is finished after the set temperature is achieved No fuel testing time during work mode Fb30 in WORK mode if temperature...

Страница 8: ...set by the producer by choosing Prod option in service mode and pressing OK button After activating this function the device sets each parameter showed in the table to default 4 9 Exiting service mode...

Страница 9: ...d if boiler overheats E 3 error means fault and overheating at the same time Appearing of E 1 error on the display without ability to cancel it by pressing STOP button in spite of temperature below 90...

Страница 10: ...10 Picture 2 RK 2001E2 connection scheme Picture 3 UM 1 module connection scheme...

Страница 11: ...2 The work mode and pause time of CH pump L 65 Minimum boiler temperature H 85 Maximum boiler temperature h 2 Boiler temperature hysteresis A 99 Boiler overheating temperature Fd60 Fuel shortage testi...

Страница 12: ...12...

Страница 13: ...13...

Страница 14: ...14...

Страница 15: ......

Страница 16: ...Producer P W KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl...

Отзывы: