CHAPTER 10: FAILURE DETECTION 

Below  you  will  find  only  general  information.  Since  different  kinds  of  failures  and/or  malfunctions  may  occur, 
please refer to experienced Service Technicians for any problem. 

Note:  chargers  with  decreasing  current  may  also  have 

seeming  malfunctions

  due  to  external  causes, 

such  as  electrical  systems  and/or  batteries  in  bad  conditions.  Take  this  into  account  when  checking 
them. 

10.1: NECESSARY INSTRUMENTS 

- Multifunctional digital tester  
- DC clamp meter  

10.2: FIRST CHECKS TO BE PERFORMED 

 

Preliminary check on the general conditions of battery charger and battery (see previous paragraph). 

 

Make  sure  that  the  power  cord  of  the  charger  has  been  properly  connected  to  mains  and  that  the  mains 
switch is OFF. 

 

Check the mains. 

 

Make sure that charger has been properly connected to battery and check the condition of connectors. 

10.3: FAILURE DETECTION AND MEASURES 

FAILURE

 

POSSIBLE CAUSES

 

REMEDIES AND/OR CHECKS TO BE PERFORMED

 

BATTERY IS CONNECTED, 
CHARGER IS POWERED, 
BUT THE CARD DOES NOT 
SIGNAL IT AND  CHARGER 
DOES NOT START 
CHARGING 

- Blown fuses  
- Defective connections 

and/or contacts 

- Defective card 

1) Check the DC output fuse F2 (battery side). 

2) Check the fuse F1 on the PBM753 card. 

3) Check the path of the charging cables making sure that 

there  are  neither  bad  contacts  on  plugs  nor 
overheatings on parts of cables or cable terminals. 

5)  Check  the  voltage  path  through  contactor,  auxiliary 

transformer,  and  card  input  connector,  making  sure 
that  a  24VAC  voltage  is  present  on  the  output  aux 
trasfo and PBM753 card input. 

See following photo

 

6) Check all, if needed, replace the PBM753 control card. 

BATTERY AND MAINS ARE 
CONNECTED,  THE 
CONTACTOR OR RELAY 
CLOSES BUT THE 
CHARGER DOES NOT 
DELIVER ANY CURRENT 

- Power failure 
- Blown fuses 
- Defective connections 

and/or contacts 

- Defective rectifier 

bridge 

1)  Check  the  phase  voltage  output  from  the  contactor 

contacts and phase voltage input to main Transformer 
(TR). 

2) Check that cables are in good conditions and there are 

no defective cables and/or terminals. 

3) Check the output fuse on battery side (F2) 

4) Check the efficiency of the rectifier bridge* (RD). 

THE BATTERY CHARGER 
DELIVERS LITTLE 
CURRENT 

- Power failure 
- Blown fuses 
- Defective connections 

and/or contacts 

- Defective rectifier 

bridge 

- Low mains voltage 
- Wrong wiring of the 

Main Transformer 

1)  Battery already charged or not completely discharged. 

2) Failure of one or more mains phases; check the mains 

fuses and the contacts of the contactor (TL). 

3)  Check  that  the  pin  for  adjustment  to  mains  (CM)  is  in 

the correct position as to the mains voltage present. 

4) Check the integrity of cables making sure that there are 

neither burnt wires nor oxidized terminals in the power 
circuit up to the charging cables. 

 5)  Check  the  condition  of  the  rectifier  bridge  (RD) 

see 

below instructions.

 

 

Содержание SE

Страница 1: ...I VIGNOLA MO ITALIA Tel 39 059 7705311 Fax 39 059 7705300 http www gruppopbm it e mail pbm gruppopbm it file Manuale SE PBM753 GB rev 1 doc TECHNICAL MANUAL FOR SE BATTERY CHARGER with PBM753 electro...

Страница 2: ...TAGE AND CHARGING STAGES 4 4 1 CARD SETTING ON BATTERY CHARGER WITHOUT BATTERY 5 CHAPTER 5 BATTERY CHARGER FUNCTIONS 5 CHAPTER 6 DESCRIPTION OF THE CHARGE 6 FLOATING CHARGE 7 7 1 BATTERY DISCONNECTION...

Страница 3: ...y charger operating range with rated voltage from 24V to 96V Card powered by mains only 24Vac ON OFF relay 24VAC 10A with contacts on connector Battery charger functions configuration jumpers set by t...

Страница 4: ...ours the automatic start of the charger is enabled 3 hours after connection to power CPR Proportional charge CI11h Safety timer set at 11 hours instead of 9 which is the default setting CF4h 4h long f...

Страница 5: ...the gassing voltage which may range between 2 3 and 2 5V cell By turning the one turn VGAS trimmer it is possible to set the gassing voltage with a very high accuracy as described in Chapter 4 1 The P...

Страница 6: ...has permanently switched to the final charge stage the LED light will not go off any more even if the battery voltage falls below 2 40V cell In this case reset the mains and make the procedure again C...

Страница 7: ...d CHAPTER 6 DESCRIPTION OF THE CHARGE Once all connections mains and battery have been performed the electronic card PBM 753 makes a lighting test of all the leds After this test just the L1 green led...

Страница 8: ...on The system is very useful during holidays and week ends since it makes it possible to keep battery charged while preventing overcharging overheating and or water consumption FLOATING CHARGE At the...

Страница 9: ...perates during the initial charge the battery charger stops the charging process and signals it by means of the red L4 LED which lights up constant To exit from all fault conditions the battery charge...

Страница 10: ...ns voltage which is too high or too low compared with the rated value may result in big differences in the current delivered by the battery charger with following malfunction of the charger and lower...

Страница 11: ...se F1 on the PBM753 card 3 Check the path of the charging cables making sure that there are neither bad contacts on plugs nor overheatings on parts of cables or cable terminals 5 Check the voltage pat...

Страница 12: ...ES REMEDIES AND OR CHECKS TO BE PERFORMED THE CHARGER DELIVERS TOO MUCH CURRENT Mains very high Adjustments not correct Battery too low Wrong wiring of the Main Transformer 1 Make sure that the charge...

Страница 13: ...ion characteristics suitable for the specific load K and D curves BURNT FUSE ON CARD Defective card or wrong power supply of the card 1 Make sure that the voltage battery is correct see Jumper J10 pos...

Страница 14: ...n aluminium sheets which act as dissipaters To achieve different current capacities the bridge is made up of a variable number of diodes positioned in parallel on the same plate To test operation of t...

Страница 15: ...anuale SE PBM753 GB rev 1 doc page 14 2 Make sure that there is an infinite diode by pointing the positive test prod on positive pole of bridge output and negative test prod on each phases input 3 Mak...

Страница 16: ...e Manuale SE PBM753 GB rev 1 doc page 15 4 Make sure that there is an infinite diode voltage by pointing the positive test prod on the phases and negative test prod on the negative output of bridge In...

Страница 17: ...130 150V CHAPTER 11 MAINTENANCE AND CLEANING All maintenance and cleaning processes have to be performed by qualified skilled and authorised personnel Since the battery charger is an electrical equip...

Страница 18: ...400 420 440V 0 24V TR Three phase transformer TA series RD Diode rectifier bridge PTSxxx E SH1 Shunt 100A 100mV or 200A 100mV P1 ON OFF green button PBM753 Electronic control card with microprocessor...

Страница 19: ...sion no 1 dd 01 02 2017 P B M S r l via Barella Z I VIGNOLA MO ITALIA Tel 39 059 7705311 Fax 39 059 7705300 http www gruppopbm ite mail pbm gruppopbm it file Manuale SE PBM753 GB rev 1 doc page 18 WIR...

Страница 20: ...ion no 1 dd 01 02 2017 P B M S r l via Barella Z I VIGNOLA MO ITALIA Tel 39 059 7705311 Fax 39 059 7705300 http www gruppopbm ite mail pbm gruppopbm it file Manuale SE PBM753 GB rev 1 doc page 19 WIRI...

Отзывы: