18
Power supply
230V, 50Hz, 5A
Maximum electric power consumption – fans
106W
Maximum electric power consumption – preheater
1000W
IP protection class
20
8.2.
Installation of the control panel
It is recommended to install control panel of the Unit in a living space (for example, in a corridor or
hall) at 1.5 – 1.6 m height from the floor for convenient access. Lay the control panel connection cable
supplied from the Unit location to the control panel location before finishing decoration works.
The maximum permissible installation distance of control panel from the Unit is 100 m. Use a flexible
mounting cable 4x0.22mm² to connect the panel, the resistance of each conductor must not exceed
40
ꭥ
.
Figure 8. Installation of the control panel
IT IS PROHIBITED
to install control panel in premises, where relative air humidity exceeds 70%.
Содержание X-Air C200
Страница 1: ...Rev 2 3 2021 04 INSTALLATION AND OPERATION MANUAL Heat Recovery Unit OXYGEN X Air C200...
Страница 2: ...1...