Figure 2. Horizontal installation diagram
7.3.
Connecting ducts
It is recommended to install outside air supply and exhaust ducts as far as possible from each other
to prevent the ingress of contaminated air back to premises. Please refer to local construction
regulations.
Make sure that outdoor humidity or precipitation will not get into the Unit, when connecting outside
air supply and exhaust ducts. Make sure that openings in the outside wall are installed lower than
corresponding ducts of the Unit. The air intake opening in the outside wall should be protected
against precipitation ingress to ventilation duct by grille or roof.
Figure 3. Air intake duct connection diagram
IMPORTANT!
At least 1° ventilation duct incline (refer to Figure 3. Air intake duct connection
diagram") should be ensured or other sufficient measures taken to prevent ingress of outdoor
humidity or precipitation into the Unit.
OXYGEN X-Air C200 left-side version
OXYGEN X-Air C200 right-side version