11
Illustr. 5.3 Connection diagram three point control
Controller
Controller
black
white
white
brown
white
blue
5.5 Heat meter connection set
The heat meter connection set is supplied with the
“Regumat”.
Extent of supply:
– 2x Connection fitting G 1 ½ male x G 1 female
– 2x Connection fitting G 1 male x G ¾ male
– 2x Seal G 1
– 2x Seal G ¾
– 1x Plug M10x1 female with O-ring
Illustr. 5.4 Heat meter connection set
Installation of a heat meter with a length of 110 mm:
– Fix the female threaded connection fittings G
3
⁄
4
with
the supplied seals to the heat meter.
– Fix the female threaded connection fittings G 1 with
the supplied seals to the mounted adapters.
– Fit the heat meter into the station with the help of
the enclosed collar nut sets.
– Remove the plug with O-ring on the supply side of
the isolating device (on supply on the right hand
side).
– Screw plug M10x1 with O-ring into the isolating
device.
– Screw flow temperature sensor of the heat meter
into the plug by use of the mounting material
supplied with the heat meter.
Illustr. 5.5 Installation heat meter connection set
Length 110 mm
Length 130 mm
Installation of a heat meter with a length of 130 mm is
carried out in the same way, but the connection fittings
G ¾ female and the corresponding seals are not
required.
5.6 Adaptation of the insertion block
Commercial heat meters may be integrated into the
product group. This calls for an individual adaptation
of the insertion block. Depending on the type of the
heat meter, different diameters can be cut out of the
insertion block. The perforations simplify cutting. If the
electronic components of the heat meter cannot be
integrated into the insulation, they have to be removed
from the heat meter and be mounted onto the wall
near the insulation. In this case, the insertion block
does not have to be adapted.
Illustr. 5.6 Insertion block with cutting for heat meter