Transmission station
with deaerator
“Regusol EL-130”
Installation instructions
Transmission station “Regusol EL-130” with pre-assembled,
integrated microprocessor-driven control.
The transmission station is supplied with a detailed
instruction manual of the control.
The “Regusol EL-130” is equipped with a deaerator for
air elimination from the heat transfer medium.
Safety notes
The safety notes are to be observed.
Installation, initial operation, maintenance and repairs
have to be carried out by authorized and qualified trade persons.
Installation notes
The transmission station is supplied pre-assembled.
Pump wiring (5) is necessary.
Compression fittings for 3/4” copper pipe are included.
The transmission station always has to be mounted at a lower
level than the collectors.
Assembly notes
Remove transmission station from the packaging.
Pull the front insulation (1) from the control retainer (2)
while pushing the control retainer against the back insulation (3).
Now the control retainer can be pulled off the back insulation
together with the control (4).
Remove transmission station (6).
For each wall-mounting device (7), drill 5/16-inch holes
at a distance of 10
5
/
16
inches.
Fix mounting device by screwing it onto the wall and engage
back insulation. Now push transmission station onto the
fixing clips of the wall mounting device.
Connect the Regusol to the collectors (top connectors) and the tank
(bottom connectors) through the Regusol compression fittings.
See diagram 1 for details. Use 3/4” hard copper to pipe. The pipe
ends must be cut at right angles and be free of burrs. Apply clear
plumber’s grease on the compression nut thread and rings. Slide in
pipe until stop and firmly tighten the compression fittings. Hold firm
while tightening.