![Oval Smart EX DELTA II Series Скачать руководство пользователя страница 35](http://html1.mh-extra.com/html/oval/smart-ex-delta-ii-series/smart-ex-delta-ii-series_instructions-manual_1662166035.webp)
D-582-3-E
35
②
Separate fitting boss (0) in the following manner:
(a) Remove C-shaped stop ring (20), O-ring retainer (208) and O-ring (20). (b) Taking off four hex
socket head setscrews (0B), remove fitting boss (0).
③
Sensor Removal
Taking off four hex socket head bolts (08) in this state, the sensor (20) can now be separated.
Do not force but pull it carefully until out.
(3) Sensor Installation
Reverse the order of steps (2) above, observing the following instructions:
CAUTION
①
When installing the sensor, make sure that the O-ring (204) is in place. If this O-ring is
distorted or otherwise damaged, replace with a new one.
②
Align the locating pin of sensor (201) with the pin slot of shaft assembly (102) and bluff
body (105). You cannot disassemble sensor (201).
CAUTION
Sensor (201) cannot be disassembled. If found to be defective, it should be replaced as an
assembly.