FOUNDATION Fieldbus-compliant ALTImass series
L-740FF-1-E
1
※
: For details, refer to Instruction Manual L-740.
5.4.1 IT Function Block Configuration
(1) Block configuration
IT function block is not capable of totalizing by itself. To use IT function block on this device, connect
(configure) output port OUT of AI function block to input port IN_1 (or IN_2) of IT function block.
(2) Parameter setting
1. OUT_RANGE
Set the range of output port OUT of AI function block (OUT_SCALE of AI function block) for sub-
parameters of OUT_RANGE such as EU_100, EU_0, UNITS_INDEX, and DECIMAL.
2. TIME_UNIT
Set the unit of time corresponding to input port IN_1 (unit of time set for output port OUT of AI function
block) for TIME_UNIT1 parameter. (To use input from IN_2, set TIME_UNIT2 likewise.)
3. INTEG_TYPE and INTEG_OPTS
Set parameters INTEG_TYPE and INTEG_OPTS depending on the purpose of IT function block.
(3) Total reset
Set "Reset" for OP_CMD_INT parameter of IT function block.