Relative
index
Parameter name
R/W
Data format
Description
47
SET_FSTATE
W
TYPE_ENUM/1
Allows fail-safe condition to be manually initiated by selecting "Set"
48
CLR_FSTATE
W
TYPE_ENUM/1
Writing a "Clear" to this parameter will clear the device faultstate
if the field condition has cleared.
49
MAX_NOTIFY
R
TYPE_U8/1
Maximum number of unconfirmed alert notify messages possible
50
LIM_NOTIFY
W
TYPE_U8/1
Maximum number of unconfirmed alert notify messages allowed
51
CONFIRM_TIME
W
TYPE_U32/4
The minimum time between retries of alert reports
52
WRITE_LOCK
W
TYPE_ENUM/1
Prohibits writing from outside
53
UPDATE_EVT.UNACKNOWLEDGED
W
TYPE_ENUM/1
Displays description of an event when update occurs
54
UPDATE_EVT.UPDATE_STATE
R
TYPE_ENUM/1
Displays report status of an update event
55
UPDATE_EVT.TIME_STAMP
R
TYPE_TIME/8
Displays the time of an update event
56
UPDATE_EVT.STATIC_REVISION
R
TYPE_U16/2
Displays the number of times update events have occurred
57
UPDATE_EVT.RELATIVE_INDEX
R
TYPE_U16/2
Displays the relative index of an update event
58
BLOCK_ALM.UNACKNOWLEDGED
W
TYPE_ENUM/1
Displays description of an alarm when a block alarm occurs
59
BLOCK_ALM.ALARM_STATE
R
TYPE_ENUM/1
60
BLOCK_ALM.TIME_STAMP
R
TYPE_TIME/8
61
BLOCK_ALM.SUB_CODE
R
TYPE_ENUM/2
62
BLOCK_ALM.VALUE
R
TYPE_U8/1
63
ALARM_SUM.CURRENT
R
TYPE_ENUM/2
Displays the alarm status of the entire block
64
ALARM_SUM.UNACKNOWLEDGED
R
TYPE_ENUM/2
65
ALARM_SUM.UNREPORTED
R
TYPE_ENUM/2
66
ALARM_SUM.DISABLED
W
TYPE_ENUM/2
67
ACK_OPTION
W
TYPE_ENUM/2
Sets acknowledge behavior of an alarm
68
WRITE_PRI
W
TYPE_U8/1
Sets the priority of WRITE_ALM
69
WRITE_ALM.UNACKNOWLEDGED
W
TYPE_ENUM/1
Displays the relative index of an update event
70
WRITE_ALM.ALARM_STATE
R
TYPE_ENUM/1
71
WRITE_ALM.TIME_STAMP
R
TYPE_TIME/8
72
WRITE_ALM.SUB_CODE
R
TYPE_ENUM/2
73
WRITE_ALM.VALUE
R
TYPE_ENUM/1
74
ITK_VER
R
TYPE_U16/2
Displays the revision number of the interoperability test case
used to register this device
75
FD_VER
R
TYPE_U16/2
The major version of the Field Diagnostics specification used for this device
76
FD_FAIL_ACTIVE
R
TYPE_ENUM/4
Field Diagnosis function (NE107):
This parameter reflects the error conditions that are being
detected as active in the "Failed" category
77
FD_OFFSPEC_ACTIVE
R
TYPE_ENUM/4
Field Diagnosis function (NE107):
This parameter reflects the error conditions that are being
detected as active in the "Off Specification" category
78
FD_MAINT_ACTIVE
R
TYPE_ENUM/4
Field Diagnosis function (NE107):
This parameter reflects the error conditions that are being
detected as active in the "Maintenance" category
79
FD_CHECK_ACTIVE
R
TYPE_ENUM/4
Field Diagnosis function (NE107):
This parameter reflects the error conditions that are being
detected as active in the "Check Function" category
80
FD_FAIL_MAP
W
TYPE_ENUM/4
Field Diagnosis function (NE107):
This parameter enables or disables the conditions to be detected
as active in the "Failed" category
81
FD_OFFSPEC_MAP
W
TYPE_ENUM/4
Field Diagnosis function (NE107):
This parameter enables or disables the conditions to be detected
as active in the "Off Specification" category
82
FD_MAINT_MAP
W
TYPE_ENUM/4
Field Diagnosis function (NE107):
This parameter enables or disables the conditions to be detected
as active in the "Maintenance" category
83
FD_CHECK_MAP
W
TYPE_ENUM/4
Field Diagnosis function (NE107):
This parameter enables or disables the conditions to be detected
as active in the "Check Function" category
84
FD_FAIL_MASK
W
TYPE_ENUM/4
Field Diagnosis function (NE107):
This parameter is used to suppress any conditions that are active in the
"Failed" category from being broadcasted through an Alarm parameter
85
FD_OFFSPEC_MASK
W
TYPE_ENUM/4
Field Diagnosis function (NE107):
This parameter is used to suppress any conditions that are active in the
"Off Specification" category from being broadcasted through an Alarm
parameter
86
FD_MAINT_MASK
W
TYPE_ENUM/4
Field Diagnosis function (NE107):
This parameter is used to suppress any conditions that are active in the
"Maintenance" category from being broadcasted through an Alarm parameter
87
FD_CHECK_MASK
W
TYPE_ENUM/4
Field Diagnosis function (NE107):
This parameter is used to suppress any conditions that are active in the
"Check Function" category from being broadcasted through an Alarm