background image

5

Outdoor Lifestyles  •  ODMEZG-36 Installation Manual  •  4601-901  Rev. B  •  10/17

H. Requirements for the Commonwealth of 

Massachusetts

For all side wall horizontally vented gas fueled equipment 

installed in every dwelling, building or structure used in 

whole or in part for residential purposes, including those 

owned or operated by the Commonwealth and where the 

side wall exhaust vent termination is less than seven (7) 

feet above finished grade in the area of the venting, in

-

cluding but not limited to decks and porches, the following 

requirements shall be satisfied:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented 

gas fueled equipment, the installing plumber or gas fitter 

shall observe that a hard wired carbon monoxide detector 

with an alarm and battery back-up is installed on the floor 

level where the gas equipment is to be installed. In addi

-

tion, the installing plumber or gas fitter shall observe that 

a battery operated or hard wired carbon monoxide detec

-

tor with an alarm is installed on each additional level of 

the dwelling, building or structure served by the side wall 

horizontal  vented  gas  fueled  equipment.  It  shall  be  the 

responsibility of the property owner to secure the services 

of  qualified  licensed  professionals  for  the  installation  of 

hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fu

-

eled equipment is installed in a crawl space or an attic, 

the hard wired carbon monoxide detector with alarm and 

battery  back-up  may  be  installed  on  the  next  adjacent 

floor level.

In the event that the requirements of this subdivision can 

not be met at the time of completion of installation, the 

owner shall have a period of thirty (30) days to comply 

with the above requirements; provided, however, that dur-

ing said thirty (30) day period, a battery operated carbon 

monoxide detector with an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each  carbon  monoxide  detector  as  required  in  accor

-

dance with the above provisions shall comply with NFPA 

720 and be ANSI/UL 2034 listed and IAS certified. 

Signage

A metal or plastic identification plate shall be permanent

-

ly mounted to the exterior of the building at a minimum 

height of eight (8) feet above grade directly in line with the 

exhaust vent terminal for the horizontally vented gas fu

-

eled heating appliance or equipment. The sign shall read, 

in print size no less than one-half (1/2) in. in size, 

“GAS 

VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB-

STRUCTIONS”.

Inspection

The state or local gas inspector of the side wall horizon

-

tally vented gas fueled equipment shall not approve the 

installation unless, upon inspection, the inspector ob-

serves carbon monoxide detectors and signage installed 

in accordance with the provisions of 248 CMR 5.08(2)(a)1 

through 4. 

Exemptions

The following equipment is exempt from 248 CMR 5.08(2)

(a)1 through 4: 
•  The equipment listed in Chapter 10 entitled “Equipment 

Not Required To Be Vented” in the most current edition 

of NFPA 54 as adopted by the Board; and 

•  Product Approved side wall horizontally vented gas fu

-

eled equipment installed in a room or structure separate 

from the dwelling, building or structure used in whole or 

in part for residential purposes. 

MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided

When  the  manufacturer  of  Product Approved  side  wall 

horizontally  vented  gas  equipment  provides  a  venting 

system design or venting system components with the 

equipment, the instructions provided by the manufacturer 

for installation of the equipment and the venting system 

shall include:
•  Detailed instructions for the installation of the venting 

system design or the venting system components; and

•  A complete parts list for the venting system design or 

venting system. 

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall 

horizontally vented gas fueled equipment does not pro

-

vide  the  parts  for  venting  the  flue  gases,  but  identifies 

“special  venting  systems”,  the  following  requirements 

shall be satisfied by the manufacturer:

•  The  referenced  “special  venting  system”  instructions 

shall be included with the appliance or equipment in-

stallation instructions; and 

•  The  “special  venting  systems”  shall  be  Product  Ap

-

proved by the Board, and the instructions for that sys-

tem shall include a parts list and detailed installation 

instructions. 

A copy of all installation instructions for all Product Ap

-

proved  side  wall  horizontally  vented  gas  fueled  equip

-

ment, all venting instructions, all parts lists for venting 

instructions,  and/or  all  venting  design  instructions  shall 

remain with the appliance or equipment at the completion 

of the installation. 

See Gas Connection section for additional Common-

wealth of Massachusetts requirements.

Note: 

The following requirements reference various 

Massachusetts and national codes not contained in this 

document.

Содержание ODMEZG-36

Страница 1: ... plate This appliance is not convertible for use with other gases unless a certified kit is used DO NOT store or use gasoline or other flam mable vapors and liquids in the vicinity of this or any other appliance What to do if you smell gas DO NOT try to light any appliance DO NOT touch any electrical switch DO NOT use any phone in your building Leave the building immediately Immediately call your ...

Страница 2: ...ion A Securing and Leveling the Appliance 13 B Installing Non Combustible Facing Material 14 C Installation Instructions for Outdoor Side 15 5 Termination Location and Vent Information A Vent Termination Minimum Clearances 17 B Chimney Diagram 18 C How to use the Vent Graph 19 D Vertical Horizontal Termination Configurations 20 E Below Grade Installations 21 F Vertical thru the roof Applicatons 22...

Страница 3: ..._ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ Gas Section 9 Pg 42 Proper appliance for fuel type Was a conversion performed Leak check performed and inlet pressure verified ed Verified proper air shutter setting for installation type ___________________________ ___________________________ ___________________________ ___________________________ ______________________...

Страница 4: ...liance must be electrically wired and grounded in accordance with local codes or in the absence of local codes with National Electric Code ANSI NFPA 70 latest edition or the Canadian Electric Code CSA C22 1 A 110 120 VAC circuit for this product must be pro tected with ground fault circuit interrupter protection in compliance with the applicable electrical codes when it is installed in locations s...

Страница 5: ... gas fu eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspector of the side wall horizon tally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector ob serves carbon monoxide detectors and signage instal...

Страница 6: ...ly the media must be installed Report to your dealer any parts damaged in shipment particularly the condition of the glass Read all of the instructions before starting the instal lation Follow these instructions carefully during the installation to ensure maximum safety and benefit WARNING Risk of Fire or Explosion Damaged parts could impair safe operation DO NOT install damaged in complete or sub...

Страница 7: ...t Dimension Diagrams Dimensions are actual appliance dimensions Use for reference only For framing dimensions and clearances refer to Figure 3 6 Location Inches Millimeters G 6 5 8 168 H 1 1 2 38 I 9 1 8 232 J 24 5 8 625 K 19 1 8 486 L 20 1 8 511 Location Inches Millimeters A 49 1 8 1248 B 41 1 2 1029 C 23 5 8 524 D 29 5 8 753 E 50 3 4 1289 F 37 3 4 959 Appliance Dimensions Table ...

Страница 8: ...y to ensure safe installation Failure to follow instructions exactly can create a fire hazard The appliance cannot be installed on a carpet tile or other combustible material other than wood flooring If installed on carpet or vinyl flooring the appliance shall be installed on a metal wood or noncombustible material panel extending full width and depth of the appliance WARNING 68 1727 mm Minimum Ce...

Страница 9: ...esign preference Figure 3 5 Appliance Locations It is important to follow the framing and finishing instruc tions step by step to ensure proper placement of fireplace in the surrounding framing finishing materials 51 3 4 Refer to Section 10 for hearth mantel and wall projection information 18 1 8 51 3 4 18 1 8 Mantel Clearances NOTE The combustible area above the facing must not protrude more than...

Страница 10: ... A B D HEADER DEPTH HEADER DEPTH APPLIANCE MAY BE INSTALLED OFF OF FLOOR Adjust framing dimensions for interior and exterior sheathing such as sheetrock and drywall Header depth not to exceed 3 1 2 inches If appliance is installed off of floor maintain required clearances to combustibles Construct platform in accordance with local building codes Clearances to Combustibles Follow these instructions...

Страница 11: ...you MUST check local building codes to determine the requirements to these steps Chases should be constructed in the manner of all outside walls of the home to prevent cold air drafting problems Walls ceiling base plate and cantilever floor of the chase should be insulated Vapor and air infiltration barriers should be installed in the chase as per regional codes for the rest of the home Additional...

Страница 12: ...immed from the floor appropriately to maintain 1 4 in minimum space between the floor hearth and hearth refractory The base of the fireplace may sit on a combustible sur face The area in front of the fireplace must be protected by a noncombustible hearth extension unless the fire place is raised a minimum of three inches above the com bustible floor or hearth See Figures 3 7 and 3 8 Figure 3 8 Non...

Страница 13: ... secure the appliance see below Nailing tabs are provided to secure the appliance to the framing members Bend out the two nailing tabs on each side Place the appliance into position Keep nailing tabs flush with the framing See Figure 4 1 Level the appliance from side to side and front to back Shim the appliance as necessary It is acceptable to use wood shims underneath the appliance Secure the app...

Страница 14: ...the side of the fireplace See Figures 3 2 3 4 for framing and clearance details Figure 4 2 Nailing Tabs Interior Side Figure 4 3 Nailing Tabs Exterior Outdoor Side NAILING TAB SHIPPING FLANGE NAILING TAB 1 IN STANDOFF Optional Secure the appliance to the floor by inserting two screws through the pilot holes at the bottom of the appliance Figure 4 4 Install Non Combustible Facing Material B Install...

Страница 15: ... used beyond 3 from the top of the flashing must be approved to a minimum of 225 F continuous exposure Special care should be taken when choosing building materials for weatherproofing i e building wraps sealant tapes liquid sealants rubberized flashings etc All sealant materials or building wraps installed within 3 of the top of the fireplace flashing must be approved to a minimum temperature of ...

Страница 16: ...flashing by 3 in Metal Flashing Top of Fireplace 3 4 in Overlap from flashing Figure 4 6 Seal this seam with caulk both sides Seal along bottom edge with caulk Facing material must overlap face by at least 3 4 in Facing must NOT extend beyond this edge NOTE Seal along bottom edge and boundary of facing material with caulk Figure 4 7 ...

Страница 17: ...SCHARGE OPENING 5 Termination Location and Vent Information Fire Risk Maintain vent clearance to combustibles as specified DO NOT pack air space with insulation or other materials Failure to keep insulation or other materials away from vent pipe could cause overheating and fire WARNING Figure 5 2 Staggered Termination Caps Gas Wood or Fuel Oil Termination Cap B Gas Termination Cap A If using decor...

Страница 18: ...MITTED C J B D B F B A E V V V V V V M H or i V G X V H A V V H Electrical Service V K V K V L C V N 6 inches non vinyl sidewalls 12 inches vinyl sidewalls O 18 inches non vinyl soffit and overhang 42 inches vinyl soffit and overhang P 8 ft QMIN RMAX 1 cap 3 feet 2 x Q ACTUAL 2 caps 6 feet 1 x Q ACTUAL 3 caps 9 feet 2 3 x Q ACTUAL 4 caps 12 feet 1 2 x Q ACTUAL QMIN termination caps x 3 RMAX 2 term...

Страница 19: ...ottom of the graph 3 Select the indicated dimension and position the fire place in accordance with same Example If the vertical dimension from the floor of the fireplace is 11 3 4 m the horizontal run to the face of the outer wall must not exceed 16 4 9 m Sidewall Vent Graph showing the relationship between vertical and horizontal dimensions for a Direct Vent flue system 40 38 36 34 32 30 28 26 24...

Страница 20: ... finished outside wall The maximum number of 90 elbows per side wall installation is three 3 A minimum of 12 305 mm is required before a 90 elbow If a 90 elbow is fitted directly after 12 305 mm vertical section mounted to the top of the fireplace the maximum horizontal vent run before the termination or a vertical rise is 36 914 mm Figure 5 5 Maximum Three 3 90 Elbows Per Installation 3 x 90 Elbo...

Страница 21: ...ace of the exterior wall See the Sidewall Venting Graph for extended horizontal run if the vertical exceeds 12 1 Establish vent hole through the wall 2 Remove soil to a depth of approximately 16 below base of snorkel Install drain pipe Install window well not supplied Refill hole with 12 of coarse gravel leaving a clearance of approximately 4 below snorkel Figure 5 9 3 Install vent system 4 Ensure...

Страница 22: ...al plane the maximum horizontal length must be reduced by 18 450 mm Example Maximum horizontal length No elbows 10 3 m 1x45 elbows 8 5 2 6 m 2x45 elbows 7 2 1 m A minimum of an 12 3 6 m vertical rise is required Two sets of 45 elbows offsets may be used within the vertical sections From 0 to a maximum of 8 2 5 m of vent pipe can be used between elbows Figure 5 12 The maximum angular variation allo...

Страница 23: ...lowed between two 45º elbows See Figure 5 13 Figure 5 14 shows the vertical and horizontal offsets for DVP elbows Figure 5 13 HORIZONTAL VERTICAL RUN RISE E F F E C T I V E L E N G T H Y X X X DVP Pipe Effective Length Rise Run Inches Millimeters Inches Millimeters DVP4 4 102 2 3 4 70 DVP6 6 152 4 1 4 108 DVP12 12 305 8 1 2 216 DVP24 24 610 17 432 DVP36 36 914 25 1 2 648 DVP48 48 1219 34 864 DVP6A...

Страница 24: ...uring Standards Vertical and horizontal measurements listed in the vent diagrams were made using the following standards Pipe measurements are shown using the effective length of pipe See Section 11 A for information on effective length of pipe components Horizontal terminations are measured to the outside mounting surface flange of termination cap see Figure 5 15 Vertical terminations are measure...

Страница 25: ...rizontal Run NOTICE Failure to follow these instructions will void the warranty WARNING This fireplace must be vented to the outside The venting system must NEVER be attached to a chimney serving a separate solid fuel burning appliance Each gas appliance must use a separate vent system Do not use common vent systems WARNING Horizontal sections of this vent system require a minimum of 3 clearances ...

Страница 26: ...0 17 Figure 5 19 Vertical Vent Maximum Note If installing a vertical vent termination off the top of the appliance the optional exhaust restrictor may be needed V V 3 ft Min 1m 40 ft Max 13 3 m Top Vent Vertical Termination No Elbows Note Use DVP Series components only ...

Страница 27: ...RNING Risk of Fire DO NOT attach elbow directly to the appliance The ODMEZG 36 requires a minimum of 12 inches of vertical venting before attaching any elbow to the appliance ODMEZG 36 V1 V2 Minimum H1 H2 Maximum 1 ft 309 mm 3 ft 2 7 m 2 ft 610 mm 5 ft 1 5 m 3 ft 914 mm 6 ft 2 8 m 4 ft 1 2 m 12 ft 3 6 m 5 ft 1 5 m 15 ft 4 5 m V1 V2 H1 H2 63 ft 19 2 m Maximum H1 H2 23 ft 7 1 m Maximum ...

Страница 28: ...1 H2 V2 V1 WARNING Risk of Fire DO NOT attach elbow directly to the appliance The ODMEZG 36 requires a minimum of 12 inches of vertical venting before attaching any elbow to the appliance ODMEZG 36 V1 V2 Minimum H1 H2 Maximum 1 ft 309 mm 3 ft 2 7 m 2 ft 610 mm 5 ft 1 5 m 3 ft 914 mm 6 ft 2 8 m 4 ft 1 2 m 12 ft 3 6 m 5 ft 1 5 m 15 ft 4 5 m V1 V2 H1 H2 63 ft 19 2 m Maximum H1 H2 23 ft 7 1 m Maximum ...

Страница 29: ...ermination cap Non Combustible Wall Penetration If the hole being penetrated is surrounded by non com bustible materials such as concrete a hole with diameter one inch greater than the pipe is acceptable Note Do not pack the gap with insulation Whenever a non combustible wall is penetrated the wall shield firestop is only required on one side and no heat shield is necessary Figure 6 1 Horizontal V...

Страница 30: ... NOT pack insu lation around the vent Insulation must be kept back from the pipe to prevent overheating ATTIC ABOVE A PIPE DVP A 10 in 254 mm A INSTALL ATTIC INSULATION SHIELDS BEFORE OR AFTER INSTALLATION OF VENT SYSTEM CEILING FIRESTOP INSTALLED BELOW CEILING CEILING FIRESTOP INSTALLED ABOVE CEILING D Install Attic Insulation Shield WARNING Fire Risk DO NOT allow loose materials or insulation to...

Страница 31: ...ating Use screws no longer than 1 2 in 13 mm If predrilling screw holes DO NOT penetrate inner pipe Required Commercial Multi family Multi level exceeding two stories or High Rise Applications All outer pipe joints must be sealed with high temperature silicone 300º F minimum continuous exposure rating in cluding the slip section that connects directly to the hori zontal termination cap Apply a bea...

Страница 32: ... slip section elbow and cap outer flues shall be sealed Maintain a 1 1 2 in 38 mm overlap between the slip section and the pipe section Secure the pipe and slip section with two screws no longer than 1 2 in 13 mm using the pilot holes in the slip section See Figure 7 6 120º Figure 7 7 Securing Vertical Pipe Sections 120º Figure 7 8 Securing Horizontal Pipe Sections C Secure The Vent Sections Verti...

Страница 33: ...17 D Disassemble Vent Sections Rotate either section see Figure 7 9 so the seams on both pipe sections are aligned as shown in Figure 7 10 Pull carefully to separate the pieces of pipe Figure 7 10 Align and Disassemble Vent Sections Figure 7 9 Rotate Seams for Disassembly ...

Страница 34: ...F TO LOWEST DISCHARGE OPENING Figure 7 13 Install Bolt into Brackets NOTICE Failure to properly caulk the roof flashing and pipe seams could permit entry of water Caulk the gap between the roof flashing and the outside diameter of the pipe Caulk the perimeter of the flashing where it contacts the roof surface See Figure 7 12 Caulk the overlap seam of any exposed pipe sections that are located abov...

Страница 35: ...nation cap shown in Figure 7 15 Heat shields must overlap 1 1 2 in 38 mm mini mum There are two sections of the heat shield One section is factory attached to the wall shield firestop The other section is factory attached to the cap See Figure 7 15 If the wall thickness does not allow the required 1 1 2 in 38 mm heat shield overlap when installed an extended heat shield must be used If the wall th...

Страница 36: ...seal as appropriate for siding material at outside edges of cap When installing a horizontal termination cap follow the cap location guidelines as prescribed by current ANSI Z223 1 and CAN CGA B149 installation codes and refer to Section 4 of this manual CAUTION Risk of Burns Local codes may require in stallation of a cap shield to prevent anything or anyone from touching the hot cap NOTICE For ce...

Страница 37: ...Risk of Shock Replace damaged wire with type 105 C rated wire Wire must have high temperature insulation Accessories Requirements This appliance may be used with a wall switch wall mounted thermostat and or a remote control Wiring for optional Hearth Home Technologies approved accessories should be done now to avoid reconstruction Follow instructions that come with those accessories Figure 8 1 Bot...

Страница 38: ...or Explosion DO NOT wire IFT controlled appliance junction box to a switched circuit Incor rect wiring will override IFT safety lockout Refer to Figure 8 3 or 8 4 IFT Wiring Diagram This appliance is equipped with an Intellifire Touch control valve which operates on a 6 volt 1 5AMP system Plug the 6 volt transformer plug into the appliance junction box to supply power to the unit OR install 4 AA c...

Страница 39: ...JUNCTION BOX 110 120 VAC RF MODULE ADAPTER I S 6 PIN RED BLK ORANGE PILOT GREEN MAIN IFT RC400 REMOTE CONTROL RED BLK BRN BRN JUMPER WIRE LIGHTING HARNESS WIRE HARNESS LIGHT JOIN INCANDESANT LIGHTING BRN ACCESSORY CABLE POWER VENT OPTIONAL Figure 8 4 IntelliFire Touch Wiring Diagram withPower Vent ...

Страница 40: ...onnected to the 1 2 in 13 mm control valve inlet If substituting for these components please consult local codes for compliance Fire Risk Explosion Hazard High pressure will damage valve Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 1 2 psig Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1 2 psig WARNI...

Страница 41: ...k of Fire or Explosion Gas build up dur ing line purge could ignite Purge should be performed by qualified service technician Ensure adequate ventilation Ensure there are no ignition sources such as sparks or open flames E High Altitude Installations NOTICE If the heating value of the gas has been reduced these rules do not apply Check with your local gas utility or authorities having jurisdiction...

Страница 42: ...ical vent run Adjust air shutter for longer vertical runs See Figure 9 4 Refer to Gas Service Access instructions in Section 9 C to access the air shutter Loosen the Philips screw Air Shutter Settings NG Propane ODMEZG 36 1 4 IN No Cap Twist shutter to adjust Shutter may be open for longer horizontal vent runs Do not close the air shutter more than 1 16 in for NG or 1 4 in for propane Tighten the ...

Страница 43: ... in a Vertical Tube Furnace at 750 ºC WARNING Risk of Fire Maintain specified air space clearances to combustibles Inadequate air space could cause overheating and fire NOTICE The maximum finishing material not only includes the decorative finish materials marble tile slate etc but also the thin set lath and adhesive used to attach the decorative finish material Finishing Materials This section di...

Страница 44: ...f Sheetrock Cracking DO Use all purpose joint compound Use eggshell paint 100 acrylic latex paint gloss or semi gloss To Avoid Sheetrock Cracking DO NOT Use a quick set or light weight joint compound Use flat paint In extreme cases lab tests have shown yellow pigments fading out of paints over time due to heat Vent run and installation location will have an effect on wall temperature and fading If...

Страница 45: ... levers Cam Levers FP2433 lift glass Figure 10 4 Remove Glass Frame DANGER HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN TO TOUCH GLASS Un panneau vitré chaud peut causer des brûlures Laissez refroidir le panneau vitré avant d y toucher Ne laisser jamais les enfants toucher le panneau vitré A barrier designed to reduce the risk of burns from the hot viewing glass ...

Страница 46: ...ight Bulbs Pilot is Located in Center Figure 10 6 Stone and Glass Placement D Glass Only Placement NOTE Three 3 bags of glass are supplied with the fireplaces It is not necessary to use the entire 3rd bag of glass provided Too much glass can cut off the proper amount of air the burner needs to burn clean This may cause sooting 1 Spread glass evenly in one layer over the entire floor and burner It ...

Страница 47: ...RIER INSTALLATION INSTRUCTIONS 1 Remove screen from packaging 2 Align the four tabs on the sides of the screen frame two top two bottom Figure 10 7 with the corre sponding slots on the firebox Figure 10 8 3 Slide the screen down into the slots until it fits secure ly in place NOTICE It is the responsibility of the installer to ensure the barrier is affixed to the fireplace at the time of instal la...

Страница 48: ...ipe see chart Effective Height Length 4 7 8 in 276 mm 10 in 254 mm 10 in 254 mm 1 in 25 mm DVP FS Ceiling Firestop 13 mm Finished Height 19 3 4 in 502 mm UNIV AS2 Attic Insulation Shield Tab 1 in 25 4 mm 20 3 4 in 527 mm 14 IN 356 MM 14 IN 356 MM 20 IN 508 MM 12 IN 305 MM DVP RDS ROOF DECK INSULATION SHIELD 10 in 254 mm 1 1 2 in 38 mm 5 in 127 mm 12 in 305 mm UP DVP HVS Vent Support Pipe Effective...

Страница 49: ... Effective Length Note Heat shields MUST overlap by a minimum of 1 1 2 in 38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield Term Cap Minimum Effective Length Maximum Effecti...

Страница 50: ...4 in 337 mm RF12 Roof Flashing Multi pak Cap Shield DRC RADIUS 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADDM Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP HPC Cap Brick Extension 13 7 8 in 352 mm 5 in 127 mm 11 7 8 in 302 mm DVP TRAPFL Flashing 26 in 660 mm DVP HSM B Extended Heat Shield 12 IN 305 mm 7 IN 178 mm 4 15 16 IN A A A 1 2 IN 13 mm 7 ...

Страница 51: ...4 mm 7 3 4 to 10 3 8 in 197 to 264 mm DVP FBHT FireBrickTermination Cap 14 in 356 mm 12 in 305 mm 12 1 8 in 314 mm 7 1 8 in 181 mm 8 3 4 in 222 mm 1 5 8 in 41 mm 16 7 8 in 429 mm DVP HPC High Performance Cap DVP TB1 Basement Vent Cap 12 in 305 mm 1 1 2 in 38 mm 7 3 8 in 187 mm 14 in 356 mm 17 3 4 in 451 mm 6 in 152 mm 13 in 330 mm 15 in 381 mm 8 1 8 in 206 mm DVP HRC SS 10 7 8 in 276 mm 10 1 2 in ...

Страница 52: ...IN 813 mm MIN 35 IN 889 mm MAX Note Use only approved termination caps with the PVI SLP See instructions included with PVI SLP kit Figure 11 5 PVI SLP Vent Components 16 IN 406 mm 15 IN 381 mm 16 11 16 IN 424 mm 9 3 16 IN 233 mm 4 1 2 IN 114 mm 16 11 16 IN 424 mm 13 5 8 IN 346 mm 12 1 2 IN 318 mm SLP LPC SLP Low Profile Cap 17 7 8 IN 454 mm 7 3 8 IN 187 mm 14 IN 356 mm 12 IN 305 mm SLP TB1 Basemen...

Страница 53: ...to order Note The PVLP SLP requires a PVLP CK be installed on this appliance The PVLP CK is ordered separately from the PVLP SLP Contact your dealer to order Figure 11 6 PVLP SLP Vent Components PVLP HS Heat Shield 14 IN 356 mm 15 1 2 IN 394 mm 11 1 2 IN 292 mm 8 IN 203 mm 4 3 8 IN 112 mm 10 IN 254 mm 5 1 4 IN 135 mm 2 1 4 IN 57 mm 9 1 2 IN 241 mm 4 3 4 IN 121 mm 2 1 4 IN 57 mm 1 1 2 IN 38 mm 6 1 ...

Страница 54: ...LP90 90 Elbow Effective Height Length SLP PIPE SLP HVS Horizontal Pipe Support SLP FS Ceiling Firestop SLP WS Wall Shield Firestop DVP SLP24 Adapter 6 1 2 in 165 mm 25 3 16 in 640 mm 8 1 16 in 205 mm 10 7 8 in 276 mm 8 7 8 in 225 mm 1 1 2 in 38 mm 8 11 16 in 220 mm 8 11 16 in 220 mm 1 1 2 in 38 mm 12 in 305 mm 12 in 305 mm 5 1 2 in 146 mm Effective Height Length Pipe inches mm SLP4 4 102 SLP6 6 15...

Страница 55: ...trol with child protection lockout feature Keep remote controls out of reach of children Contact your dealer if you have questions Printed in U S A Copyright 2016 Outdoor Lifestyles a brand of Hearth Home Technologies 7571 215th Street West Lakeville MN 55044 www outdoorlifestylesproducts com Please contact your Outdoor Lifestyles dealer with any questions or concerns For the location of your near...

Отзывы: