Modbus TCP/IP

Modbus TCP port (internal registers) 

5 0 2   > 

Max  connections 

5  >

Idle timeout 

0  >

Allowed address 

0.0.0.0  >

Function active 

On  >

Modbus TCP_IP_Gateway 

  >

SNMP

IP address                                                                            >

Functon active                                                                          On  >

Modbus TCP slave (server) settings are changed via Modbus TCP/IP 

settings. It is possible to communicate with an Ouflex device and the 

Modbus/RTU slave devices connected to it via Modbus TCP/IP interfa-

ce.

Modbus TCP port (internal registers):

 Port number 502 is reserved 

for communication of Ouflex device.  Information of Modbus registers 

of Ouflex device are read through this port. Recommendation is that 

they should not be changed unless there is a compelling reason.   

Max connections:

 It is possible to decrease server load by changing 

this setting that defines the maximum number of simultaneous con-

nections from different IP addresses to the server. Recommendation is 

that they should not be changed unless there is a compelling reason.

Idle timeout:

 This setting defines the time after which the server clo-

ses an inactive connection. Recommendation is that they should not 

be changed unless there is a compelling reason.

Allowed address:

 It is possible to improve the information security 

of the system by taking permitted connection address into use. If the 

value is 0.0.0.0, connections to the server are permitted from any IP 

address. If you define one permitted connection address, connections 

to the server are not permitted from any other IP address.

Function active:

 This selection either enables or disables the entire 

Modbus/TCP communication.

A1,B1

Port 1

Port 2

Port 3

A2,B2

Modbus TCP/IP settings

System settings > Network settings -> Modbus TCP/IP

System settings > Network settings -> SNMP

System settings > Network settings -> Modbus TCP/IP-> Modbus TCP/IP gateway

 

System settings > Network settings -> Modbus TCP/IP-> Devices

System settings > Network settings -> Modbus TCP/IP-> FTP

Port 1 (2,3) number

: It is possible to connect three Modbus/RTU 

buses to an Ouflex device. Each bus has its own port address that 

is used to communicate with bus devices via Modbus/TCP interfa-

ce. Port 1 setting defines the TCP/IP port that functions as a gateway 

to Ouflex I/O extension bus. Ouflex device is located in Modbus 1 in 

address 1. 
Port 2 defines the TCP/IP port for Modbus 2 (A1,B1). Similarly, port 3 

defines the TCP/IP port for Modbus 3 (A2,B2).  

 

SNMP settings:

 SNMP function can be used to send notifications 

about alarms activating, inactivating and being acknowledged via 

SNMP protocol to a desired server. If the SNMP trap reception does 

not ack back from Ounet to device, Ouflex sends SNMP messages 
again

 The retransmission is limited to max 240 pieces. By setting  a 

setting value of RetryDelay to 0, the retransmission is not performed.

IP address:

 The IP address of the target server to which messages 

are sent.

Active: 

This selection either enables or disables the entire SNMP function.

Devices

Ouflex 2 

IP address                                                                          >
Port 

502   >

FTP 

Ouflex device support also FTP but read only mode. So cases this can 

be use to read Modbus template files fron device to Ounet.

Two Ouflex devices can communicate with each other at the level of 

IP by using Modbus TCP protocol. In this case, two Ouflex device may 

have common points.

 For example, the outside temperature measure-

ment, or the emergency stop switch can be common. Here you can see 

what is in the name of the device, IP address and port number.

Содержание Outflex

Страница 1: ...nables installation to most common cabinets Detachable strip connectors make installation easier Key words Active alarms Alarm history KEY WORDS Internet based on line control room for professional re...

Страница 2: ...can hide them again by pres sing OK for a few of seconds Hiding information that you seldom need to change or look into makes the HMI simpler When visible this information is shown indented There may...

Страница 3: ...set alarm history 10 2 4 Routing schedule 11 2 5 Alarm parameters 12 2 6 Alarm receivers 12 3 Point information 13 3 1 Wiring info 13 3 2 Bus points 13 3 3 Time programs 13 3 3 1 Present value 13 3 3...

Страница 4: ...ast three days Hours and minutes can be set separately 1 Set hours and press OK to accept 2 Set minutes and press OK to accept 3 Press Esc to cancel and exit if needed 1 Set day and press OK to accept...

Страница 5: ...oller strip connec tor 93 red and GND black or or straight to modem own transformer Error Use the SIM card in your phone and check if the SIM card is locked PUK code PIN error Enter Ouflex controller...

Страница 6: ...etting the IP address via DHCP function 1 Go to DHCP and press OK 2 Select On and press OK to accept selection 3 Wait approximately one minute If DHCP is still Off after one minute setting the IP addr...

Страница 7: ...al number of the Ouflex device After that you have to activate the ACCESS service from the device OUMAN ACCESS device can be connected to LAN if following condi tions are fulfilled 1 LAN is routed to...

Страница 8: ...2 B2 Modbus TCP IP settings System settings Network settings ModbusTCP IP System settings Network settings SNMP System settings Network settings ModbusTCP IP ModbusTCP IP gateway System settings Netwo...

Страница 9: ...e function Description Ouflex device asks you to enter the current code The factory setting of lock code is 0000 Turn the control knob and press OK to accept each number Press ESC to return to the pre...

Страница 10: ...10 11 42 Sensor fault H1 Supply w 02 12 2010 11 22 40 Sensor fault H2 Return w 2 ALARM HISTORY Deviation alarm PR 1 GROUP 1 H1 Supply water temp 10 2 C Received 08 11 2014 02 27 Press OK to acknowled...

Страница 11: ...tch time 1 Press OK at the Add new row 2 Press OK Set the switch time for alarm routing set hours and mi nutes separately and press OK 3 Press OK and then turn the control knob to set the alarm team o...

Страница 12: ...the alarms can be found there Each application has its own alarm parameter folder A person who knows the service code can change the alarm parameters Typical alarm parameters are Alarms Alarm paramete...

Страница 13: ...pressing OK in the row of a specific bus devi ce you will see those points which has been taken into use of the bus device Points are grouped in such a way that the first sample of a univer sal inputs...

Страница 14: ...An editing view opens and it shows all the switch times and also the states into which the function is driven at these times on the chosen days Turn the control knob to browse a weekly program If you...

Страница 15: ...ate for the program then the time and mode You can select from the following 3 Select if the exception schedule repeats or not If you select re peat it can be repeated every month same time or every y...

Страница 16: ...ode that is normally used If your app lication allows the change of control mode you may change auto matic control to manual control here When you are in the manual control mode the hand symbol appear...

Страница 17: ...1 Name of room 2 Room 2 Move to the title you wish to rename and press OK A naming view opens Turn the control knob and accept each letter by pressing OK Move to the next square by pressing OK Return...

Страница 18: ...rs make installation easier Control knob and OK button Home button Not in use Detachable connector shield Detachable strip connector shield Acknowledge alarm button Alarm led Display connector RJ 45 c...

Страница 19: ...s 41 24 Vac operating voltage output GND 63 0 10 V output 41 24 Vac operating voltage output GND 64 0 10 V output 41 24 Vac operating voltage output GND 65 0 10 V output 41 24 Vac operating voltage ou...

Страница 20: ...ll show information about the latest alarms Informative messages Change of the setting value by text message Change of the selection by text message Informative messages can not be edited or sent back...

Страница 21: ...ork device to modem Modem is on but it is not ready for use Make sure that Ouflex and GSM modem SIM card have the same PIN code if PIN inqui ry is in use Modem is ready for use Modem is either sending...

Страница 22: ...r waste to prevent damage caused by un controlled waste disposal to the environment and the health of fellow human beings The users must contact the retailer responsible for having sold the product th...

Страница 23: ...ith change over contact 4 pcs relay outputs with normally open contact 4 pcs 24 Vac Triac outputs Flex Combi 32 isaDIN rail attachableandRS 485 connecteduniver sal I O extension unit It has comprehens...

Страница 24: ...6pcsrelayoutputs 2withchange overcontact 4withnormallyopencontact 4 pcs 24 Vac Triac outputs Operating voltage outputs 5 pcs 24Vac outputs and a 15 Vdc output 21I Opoints 9 pcsuniversalmeasurementinpu...

Отзывы: