16

 Settings

Supply water min limit 

12.0 °C  >

     Min lmt increase outd. temp. -20 

3.0 °C  >

Supply water max limit 

42.0 °C  >

 

 I-control ’s max effect on supp. wtr 

2.0 °C  >

 Asetusarvot

Huonelämpötila 

21.0 °C  >

Lämmönpudotus ( huonelämpö ) 

1.5 °C  >

Suuri lämmönpudotus ( huonelämpö ) 

5.0 °C  >

Menoveden minimiraja 

12.0 °C  >

 Settings

Room temperature 

21.0 °C  >

Temperature drop (room temperature ) 

1.5 °C  >

Big temperature drop (room temperature ) 5.0 °C  >
Supply water min limit 

12.0 °C  >

In Ouflex, settings can be classified into the following categories: 
•  Main settings

•  Hidden settings 

You can hide/show these settings by pressing OK for a few se-
conds. When visible, these settings are shown slightly indented.

•  Settings that require maintenance code 

There is a   symbol in front of these settings. If you try to change 

one of these settings, your Ouflex device asks you to enter the 
maintenance code.  

Changing a setting: 

Choose the desired setting by turning the control knob. Press OK to go 

to the view where editing is possible. Change the setting.

Press OK to accept the change. 

Press Esc to exit the editing view.

You can see the setting range (minimum and maximum value), if there 

is one, in the editing view.

Locking the settings: 

Lock the settings to prevent unauthorized persons from changing them. 

The device will then ask for lock code before it let’s you change the set-

tings. You can lock the settings in Ouflex device system settings. 

 Huonelämpötila

21.0°C

min: 0.0  max: 95.0

  Room temperature

21.0°C

min: 0.0  max: 95.0

Automatic control is the mode that is normally used. If your app-

lication allows the change of control mode, you may change auto-

matic control to manual control here.
        When you are in the manual control mode, the hand symbol 

appears.  

4 Settings

5 Measuring point control/manual control

Relay control

      Automatic

      Manual control

H1 Control mode

       H1 valve control                                                25 % >

 

 

If a GSM modem is connected to Ouflex device and the setting values have been brought into SMS interface, you can edit 
settings by text message. Send a message “ Key words”. The reply message shows you which key words are in use in the 
application. The example below describes the communication principle. 

If a GSM modem is connected to Ouflex device and the setting values have been brought into SMS interface, you can edit 
settings by text message. Send a message “ Key words”. The reply message shows you which key words are in use in the 
application. The example below describes the communication principle. 

R1 relay control

R1 RELAY CONTROL:
*Automatic / ON /OFF

Esimerkki

Send a message: H1 Settings.

 

The controller sends the main settings to your mobile phone. Editing the setting 
values: write the new setting in place of the old setting and send a message
back to the controller. The controller sends the setting as a return message.

H1 SETTINGS

H2 SETTINGS

H1 Settings:
Room temperature  = 21.5°C/
Temp.drop = 3.0°C/

Send a message: R1 Relay control

The controller sends a return message in which a * appears in front of the control 
mode in use. If you want to change the control mode, move the *
in front of the desired control mode and send the message back to the controller. 
The controller
will then send a return message showing that it has switched to the desired control 
mode.

Содержание Outflex

Страница 1: ...nables installation to most common cabinets Detachable strip connectors make installation easier Key words Active alarms Alarm history KEY WORDS Internet based on line control room for professional re...

Страница 2: ...can hide them again by pres sing OK for a few of seconds Hiding information that you seldom need to change or look into makes the HMI simpler When visible this information is shown indented There may...

Страница 3: ...set alarm history 10 2 4 Routing schedule 11 2 5 Alarm parameters 12 2 6 Alarm receivers 12 3 Point information 13 3 1 Wiring info 13 3 2 Bus points 13 3 3 Time programs 13 3 3 1 Present value 13 3 3...

Страница 4: ...ast three days Hours and minutes can be set separately 1 Set hours and press OK to accept 2 Set minutes and press OK to accept 3 Press Esc to cancel and exit if needed 1 Set day and press OK to accept...

Страница 5: ...oller strip connec tor 93 red and GND black or or straight to modem own transformer Error Use the SIM card in your phone and check if the SIM card is locked PUK code PIN error Enter Ouflex controller...

Страница 6: ...etting the IP address via DHCP function 1 Go to DHCP and press OK 2 Select On and press OK to accept selection 3 Wait approximately one minute If DHCP is still Off after one minute setting the IP addr...

Страница 7: ...al number of the Ouflex device After that you have to activate the ACCESS service from the device OUMAN ACCESS device can be connected to LAN if following condi tions are fulfilled 1 LAN is routed to...

Страница 8: ...2 B2 Modbus TCP IP settings System settings Network settings ModbusTCP IP System settings Network settings SNMP System settings Network settings ModbusTCP IP ModbusTCP IP gateway System settings Netwo...

Страница 9: ...e function Description Ouflex device asks you to enter the current code The factory setting of lock code is 0000 Turn the control knob and press OK to accept each number Press ESC to return to the pre...

Страница 10: ...10 11 42 Sensor fault H1 Supply w 02 12 2010 11 22 40 Sensor fault H2 Return w 2 ALARM HISTORY Deviation alarm PR 1 GROUP 1 H1 Supply water temp 10 2 C Received 08 11 2014 02 27 Press OK to acknowled...

Страница 11: ...tch time 1 Press OK at the Add new row 2 Press OK Set the switch time for alarm routing set hours and mi nutes separately and press OK 3 Press OK and then turn the control knob to set the alarm team o...

Страница 12: ...the alarms can be found there Each application has its own alarm parameter folder A person who knows the service code can change the alarm parameters Typical alarm parameters are Alarms Alarm paramete...

Страница 13: ...pressing OK in the row of a specific bus devi ce you will see those points which has been taken into use of the bus device Points are grouped in such a way that the first sample of a univer sal inputs...

Страница 14: ...An editing view opens and it shows all the switch times and also the states into which the function is driven at these times on the chosen days Turn the control knob to browse a weekly program If you...

Страница 15: ...ate for the program then the time and mode You can select from the following 3 Select if the exception schedule repeats or not If you select re peat it can be repeated every month same time or every y...

Страница 16: ...ode that is normally used If your app lication allows the change of control mode you may change auto matic control to manual control here When you are in the manual control mode the hand symbol appear...

Страница 17: ...1 Name of room 2 Room 2 Move to the title you wish to rename and press OK A naming view opens Turn the control knob and accept each letter by pressing OK Move to the next square by pressing OK Return...

Страница 18: ...rs make installation easier Control knob and OK button Home button Not in use Detachable connector shield Detachable strip connector shield Acknowledge alarm button Alarm led Display connector RJ 45 c...

Страница 19: ...s 41 24 Vac operating voltage output GND 63 0 10 V output 41 24 Vac operating voltage output GND 64 0 10 V output 41 24 Vac operating voltage output GND 65 0 10 V output 41 24 Vac operating voltage ou...

Страница 20: ...ll show information about the latest alarms Informative messages Change of the setting value by text message Change of the selection by text message Informative messages can not be edited or sent back...

Страница 21: ...ork device to modem Modem is on but it is not ready for use Make sure that Ouflex and GSM modem SIM card have the same PIN code if PIN inqui ry is in use Modem is ready for use Modem is either sending...

Страница 22: ...r waste to prevent damage caused by un controlled waste disposal to the environment and the health of fellow human beings The users must contact the retailer responsible for having sold the product th...

Страница 23: ...ith change over contact 4 pcs relay outputs with normally open contact 4 pcs 24 Vac Triac outputs Flex Combi 32 isaDIN rail attachableandRS 485 connecteduniver sal I O extension unit It has comprehens...

Страница 24: ...6pcsrelayoutputs 2withchange overcontact 4withnormallyopencontact 4 pcs 24 Vac Triac outputs Operating voltage outputs 5 pcs 24Vac outputs and a 15 Vdc output 21I Opoints 9 pcsuniversalmeasurementinpu...

Отзывы: