PRODUCT SETTINGS AND CONFIGURATION
OI-6000-X-X-X-X-O OPS_GUIDE_REV 3.1
31
If the fault terminal cannot be used, Otis Instruments recommends one of the following configurations:
Recommended Configurations for Relay Fail-Safe Setting
Power Source
Relay Wiring
Fail-Safe Outcome
OI-6000
Normally-Closed (NC) No (Off)
Normal Operation: Closed
Alarm Activation: Open
OI-6000
Normally-Open (NO)
Yes (On) Normal Operation: Closed
Alarm Activation: Open
External Power Supply Normally-Closed (NC) Yes (On) Normal Operation: Open
Alarm Activation: Closed
External Power Supply Normally-Open (NO)
Yes (On) Normal Operation: Closed
Alarm Activation: Closed
3.8.1
RELAY 1: FAIL-SAFE SETTING
1.
Use the ADD and SUB buttons to select the desired fail-safe setting for Relay 1. Select “Yes” to turn
the fail-safe setting on, or select “No” to leave the fail-safe setting off.
2.
Press the MENU button to select the desired setting and to advance to the Relay 2 fail-safe setting
screen.
3.8.2
RELAY 2: FAIL-SAFE SETTING
1.
Use the ADD and SUB buttons to select the desired fail-safe setting for Relay 2. Select “Yes” to turn
the fail-safe setting on, or select “No” to leave the fail-safe setting off.
2.
Press the MENU button to select the desired setting and to advance to the Calibration Method setting
screen.