5.3
PRODUCT TROUBLESHOOTING
OI-6000 Fault Codes
Problem
Cause(s)
Solution(s)
F1
Check
Sensor
Cable
1. The control board has lost communication with
the digital sensor interface adapter board.
1. Check connection between the sensor
housing connector header and the digital
sensor interface adapter board plug-in.
2. Replace the sensor interface adapter
board
F4
Check
Sensor
Board
1. The control board has lost communication with
the sensor interface board.
1. Replace the sensor interface board.
F5
Try to
Null
Again
1. The unit did not null correctly, due to:
• the presence of gas,
• a sensor error, or
• a sensor interface board error.
1. Re-null the device in clear air.
2. Replace the sensor element.
3. Replace the sensor interface board.
F6
Try to
Calibrate
Again
1. The unit did not calibrate correctly, due to:
• the absence of gas,
• a sensor error, or
• a sensor interface board error.
1. Recalibrate the sensor element and verify
that gas is present during calibration.
2. Replace the sensor element.
3. Replace the sensor interface board.
F14
Check
Radio
1. The sensor assembly has lost communication
with the Primary Monitor
• Network ID is incorrectly configured.
• Sensor assembly is obstructed/too far from the
Primary Monitor.
• Radio module is not working in the sensor
assembly
1. Check that the Network ID on the sensor
assembly matched the Primary Monitor
Network ID
2. Move the sensor assembly away from the
obstruction or use a high gain antenna.
3. Replace sensor radio module.
When replacing the sensor element, the detector must be nulled and calibrated.
System faults will activate the fault terminal on the device.