INSTALLATION AND STARTUP
OI-6000-X-X-X-X-O OPS_GUIDE_REV 3.1
9
5.
Locate the sensor terminal block on the control board and complete the following:
a.
Connect the power (WHITE) wire to the “+12 to +35 VDC” terminal.
b.
Connect the ground (BLACK) wire to the “GND” terminal.
OTIS MONITOR
SENSOR TERMINALS
OI-6000
POWER TERMINALS
+12 to +35 VDC WHITE +12 to +35 VDC WHITE
GND
BLACK
GND
BLACK
4-20 mA
4-20 mA
NOTICE
Wiring power to the device is the ONLY requirement for the OI-6000 to operate. With the provision of
power, the unit will function normally, indicating the presence of toxic gas at the sensor and providing
the gas level reading on the display screen. To utilize the added functionality of the device, additional
wiring is necessary. If an Otis Monitor is not used, the OI-6000 can be powered from any +12 to +35
VDC power supply that is capable of supplying at least 250 mA.