58
S E R V I C E M E N U : “ R E G U L A T I O N M O D E ”
3 different types of regulation modes can be used.
• At a
constant supply air regulation
the temperature sensor (GT7) is placed in the supply air duct and
a constant incoming air temperature is obtained.
• At
room regulation
a sensor (GT8) is placed in the room and a sensor (GT7) in the supply air duct
(minimum/maximum limitation) and a constant room temperature is obtained (suitable when
a cooling coil is installed).
• The
extract air regulation
works in a similar way as the room regulation with the difference being that
the temperature is measured in the extract air duct.
Press again and then in order to choose
Supply reg., Extract reg.
or
Room reg.
S E R V I C E M E N U : “ M O D B U S ”
Menu
”Modbus”
appears only in v wireless control unit.
V wireless control unit activates the Modbus port on the control board and the ability to communicate
via RS485. For this you need complete Modbus index that you can download from www.ostberg.com.
ID and baud rate must match the client settings.
Modbus Id
1
9600 Baud
Modbus Id
1
9600 Baud
Modbus Id
1
9600 Baud
Device name
Device name
Done Clear
1/128
Modbus
Extract reg.
Supply limits
Regulation mode
Modbus
Freeze protection
1270411_utg4_HERU_LP_SV_EN.indd 58
2019-03-04 08:16:09
1270411_utg4_HERU_LP_SV_EN.pdf 58
2019-03-04 08:20:50
Содержание HERU LP
Страница 1: ...SVENSK ENGLISH VERSION Montage installationsanvisning Assembly Installation instructions HERU LP...
Страница 10: ...10 REGLERSCHEMA HERU LP som visar samtliga givare fl desriktning h ger...
Страница 32: ...32...
Страница 33: ...33...
Страница 44: ...44 CONTROL DIAGRAM HERU LP shows all sensors flow direction right...
Страница 66: ...66 66...
Страница 67: ...67 67...
Страница 76: ...76 WIRING DIAGRAM KOPPLINGSSCHEMA 4040200 HERU 50 90 LP EC A A With electrical heater Med elv rmare...
Страница 77: ...77 WIRING DIAGRAM KOPPLINGSSCHEMA 4040201 HERU 50 90 LP EC C C Without electrical heater Utan elv rmare...
Страница 78: ...78...
Страница 79: ...79...