40
SCHEMATIC DIAGRAM FOR HERU
®
LP PLACED IN A WARM SPACE
The HERU
®
LP should be installed according to pictures
A-C
.
Allowances must be made to access the unit for servicing or maintenance.
PLACING THE HERU
®
LP UNIT
The control board of the unit is equipped with a
3-pole RS485 interface and is located on one short
end of the control board. The terminal is marked
with ‘A’, ‘B’ and ‘0’.
Three conductors are used to connect; two of the
binary data signal at the terminals ‘A’ and ‘B’, and
one conductor at the terminal for signal reference
marked ‘0’.
If no conductor is connected on terminal ‘0’ bet-
ween the control system and the unit, there is a risk
for a voltage potential between the unit and the
external control equipment, which can result that
the unit’s control board and/or the external control
equipment is damage.
The data protocol Modbus RTU is used for RS485 .
The external control equipment must support that
data protocol to commucate with the unit.
The hardware of the control board is prepared for
Modbus, but the feature is not enabled by default.
It can be activated with the Modbus compatible
remote control and then synchronized with the unit
which enables activation of the Modbus features.
For more information about configuring the Modbus
via the remote control, see chapter: Menu ”Service
Menu” and Modbus on page 58.
CONNECTING THE MODBUS TO EXTERNAL CONTROL EQUIPMENT
C D
A B
Allowances must be made to access the unit tor servicing or maintenance.
0
0
HERU unit
Control unit
Intake grille
Fresh air duct
Silencer
Supply air duct
Extract air duct
Exhaust air duct
Roof terminal
Cooker hood
✓
✓
X
✓
1270411_utg4_HERU_LP_SV_EN.indd 40
2019-03-04 08:15:48
1270411_utg4_HERU_LP_SV_EN.pdf 40
2019-03-04 08:20:44
Содержание HERU LP
Страница 1: ...SVENSK ENGLISH VERSION Montage installationsanvisning Assembly Installation instructions HERU LP...
Страница 10: ...10 REGLERSCHEMA HERU LP som visar samtliga givare fl desriktning h ger...
Страница 32: ...32...
Страница 33: ...33...
Страница 44: ...44 CONTROL DIAGRAM HERU LP shows all sensors flow direction right...
Страница 66: ...66 66...
Страница 67: ...67 67...
Страница 76: ...76 WIRING DIAGRAM KOPPLINGSSCHEMA 4040200 HERU 50 90 LP EC A A With electrical heater Med elv rmare...
Страница 77: ...77 WIRING DIAGRAM KOPPLINGSSCHEMA 4040201 HERU 50 90 LP EC C C Without electrical heater Utan elv rmare...
Страница 78: ...78...
Страница 79: ...79...