background image

6

INSTALLATION AND SAFETY

USE

 

• For an optimal indoor climate and to avoid moisture damage in the property, 

 

  there must be continuous and adequate air exchange. The unit 

must

 be run-

 

  ning continuously and only stopped for service. 

 

  The airflow is controlled via various settings on the control panel:

 

 

Reduced 

– Reduced airflow, can be used when no one is in the property.

 

 

-

 Normal

 – This is set by the installer and should not be changed by the user.

 

 

-

 Boost

 – Higher airflow than normal, medium/max can be selected. This 

 

    should be used when the load on the property is higher than what the 

 

    standard mode is set for, e.g. when there are more people than normal in 

 

    the property. 

 

• When installing HERU

®

, follow applicable regulatory requirements and 

 

  recommendations concerning location, access, duct insulation, etc. 

 

• The user may, in accordance with IEC 60335-2-40, independently perform 

 

  the service and maintenance on HERU

®

 that is described in this user manual. 

 

  However, the unit must be disconnected from any power supply before all 

 

  such work. With reservation according to IEC 60335-2-7.12 ”This appliance is 

 

  not intended for use by persons (including children) with reduced physical, 

 

  sensory or mental capabilities, or lack of experience and knowledge, unless 

 

  they have been given supervision or instruction concerning use of the appli-

 

  ance by a person responsible for their safety. Children should be supervised to 

 

  ensure that they do not play with the appliance.”

 • 

HERU

®

 should be kept in a sheltered and dry environment during storage 

  

before 

installation.

 

• Dimensioned airflow should not exceed 75% of the unit’s maximum capacity.

 

• Check regularly to ensure that supply air and extract air are functioning 

  

properly.

 • 

To avoid condensation in the unit in cold weather, the unit should not be 

 

  turned off for a prolonged period of time. 

If the unit is installed during cold 

 

  weather and not operated immediately, the ducts should be plugged to pre-

  

vent 

condensation.

SAFETY

 

• Maintenance and operation of the unit may only be performed by personnel 

 

  who have the requisite knowledge concerning maintenance of the ventilation 

 

  unit and who have read this manual.

 

• Consider the weight of the unit when installing. See technical specification for 

  

weight 

data.

 

• Bear in mind that HERU

®

 and the fan housing may have sharp corners and 

  

edges. 

 

• Before commissioning, make sure there are no foreign objects inside the unit 

 

  which could cause serious injury or damage to the unit.

 

• Always follow the electrical safety regulations concerning free clearance for 

 

  control cabinets and electric heaters.

 

• Make sure that the unit is always locked and that the keys are stored in a 

 

  location that is not accessible to unauthorized persons.

 

• Do not open the service doors while the unit is in operation. Overpressure 

 

  from the fans could cause the doors to swing open.

 

• The unit should be fitted with a locking safety switch placed nearby.

 

• Turn off the unit via the control panel and wait two (2) minutes before 

 

  opening the service doors 

 

• The safety switches must be switched off and locked before starting any 

  

service 

work. 

 

• Do not use the safety switches for normal start and stop of the unit. 

 

• Electrical installation, electrical and mechanical work and work inside the unit 

 

  and its peripheral equipment may only be performed by certified electricians 

 

  or personnel designated by H. Östberg AB.

 

• Note that the surfaces of the unit may be cold in winter conditions. 

 • 

HERU

®

 contains 

rotating parts that could cause serious injury in the event 

  

of 

contact

. The unit must therefore be connected to a duct, the doors closed 

 

  and locked and the key removed.

 • 

The heating coil in the unit could cause burns.

 The heating coil may still be 

 

  hot after the voltage has been switched off for service, maintenance and repair 

 

  work (approx. 60°C).

1270466_utg3_HERU_400_1200_eng.indd   6

2020-10-28   11:59:38

1270466_utg3_HERU_400_1200_eng.pdf   6

2020-10-28   12:04:17

Содержание HERU 1200 S EC

Страница 1: ...Other languages in digital format can be downloaded at www ostberg com HERU 400 1200 S T INSTALLATION EN...

Страница 2: ...M 16 FUNCTIONS 16 6 1 LCD 16 6 2 Up S Down T and ENTER 16 6 3 Info i 16 6 4 Info i LED display 17 6 5 Alarm 17 6 6 Alarm LED display 18 6 7 ESC 18 CONNECTING HMI 18 SCREEN LAYOUT 19 6 8 Screen 19 6 9...

Страница 3: ...essure regulation 45 10 1 Designations and measuring ranges of the pressure sensors 45 PRESSURE SENSOR QBM68 45 10 2 Settings and connections 45 10 3 Assembly 45 10 4 Pressure regulation addressing of...

Страница 4: ...rning or installation instructions or investigation of such are not cove red by the warranty The warrantor is only responsible for the function if approved accessories are used The warranty does not c...

Страница 5: ...s with stringent demands for high temperature efficiency low energy consumption low sound level high operating reliability HERU is equipped with a non hygroscopic aluminium rotary heat exchanger locat...

Страница 6: ...r a prolonged period of time If the unit is installed during cold weather and not operated immediately the ducts should be plugged to pre vent condensation SAFETY Maintenance and operation of the unit...

Страница 7: ...he fresh air and exhaust air ducts should always be condense insulated 4 If a heating coil is connected a damper motor with spring return must be mounted in the fresh air duct 5 Connect the electrical...

Страница 8: ...he unit without the filters Ensure that HERU is installed correctly Make sure that all ducts water pipes and electrical connections are correctly assembled Make sure no objects or dirt are left behind...

Страница 9: ...to be held accountable for any discrepancies that may appear in this document and also reserves the right to modify data and design ABBREVIATIONS F rkortning F rklaring BMS Building Management System...

Страница 10: ...ID Description GT1 Temp sensor supply air GT2 Temp sensor extract air GT3 Temp sensor outside air GT42 Temp sensor exhaust air GT8 Freeze protection sensor GT9 Overtemp sensor GTR Temp sensor room air...

Страница 11: ...the rotor is insufficient 2 Cooling recovery and or regulated cool down The rotary heat exchanger starts if the extract air temperature is lower than the outside temperature Regulated cool down If th...

Страница 12: ...cool down the electric heater ST1 and ST2 remains open during cool down ROTARY HEAT EXCHANGER Time controlled blow off when the unit is stopped or when heating is not required The control is integrat...

Страница 13: ...e switch program must be in OFF mode Outside temperature is higher than min outside temperature Outside temperature is lower than the difference between the room extract air temperature minus 1K Room...

Страница 14: ...be boosted to a higher flow at higher PPM RH ALARMS Deviation alarm GT1 GT2 GT3 GP1 GP2 GP3 GP4 GF1 and GF2 Recovery alarm rotor control EMS Fan alarm Freeze protection sensor GT8 Overheating electri...

Страница 15: ...lus Rights for all menus and system settings If password 2000 must be used the utmost caution should prevail There is a high risk that a change may damage basic settings configurations PUMP MONITORING...

Страница 16: ...er values etc UPS DOWNT AND ENTER 2 3 4 Buttons for menu navigation Maneuver with Pos 2 UPS Pos 3 DOWNT Pos 4 Select with ENTER Change the parameter values Open the value you would like to change by p...

Страница 17: ...is mode the outputs parameter values and signals are not controlled auto matically When any of the signals or values are set in manual mode the utmost caution must prevail All use of manual control of...

Страница 18: ...splice block Type female female RJ45 should be X marked ALARM LED DISPLAY 6 The LED display may indicate the following No lit LED No alarm Red flashing LED One or more alarms are triggered Red steady...

Страница 19: ...ation arrow X Press ENTER DISPLAY ROW The option is shown with a dark background even when viewed in read only mode Current value of the option is shown The navigation arrow is not shown in read only...

Страница 20: ...arrow UPS or DOWNT Choose Done Press ENTER or Keep the old value and close the preferences page Press ESC The scale above shows the minimum and maximum values that can be set Changing set values Chang...

Страница 21: ...re than 3 seconds to be linked directly to Password handling This is possible to do from anywhere in the menu to be linked to Password handling and then for log in or out After logged in you will be l...

Страница 22: ...be executed The enabled alarm will be shown on the row below confirm reset In this mode the red LED on the ALARM button has a steady light Troubleshoot to determine why the alarm will not reset For h...

Страница 23: ...rmula Setp comf heating Dead zone Cooling setpoint If the temperature increase above the cooling setpoint HERU CX will switch over to cooling regulation A normal dead zone value is 2 C Setp econ heati...

Страница 24: ...stop times The following options can be shown Selections manual operation Temp regulation acc to setpoint Fan control regulation acc to setpoint Auto See Time switch program chap 5 See Time switch pr...

Страница 25: ...s no significance Operation will continue switched off Off until the next day of the week Time 1 00 00 according to the value that Value 1 has this day e Time 2 with associated Value 2 i e 06 00 Comf...

Страница 26: ...m the unit operates with normal flow and then steps down to reduced flow The unit stops again at 21 00 9 pm Program according to the following COPY MONDAY TIMES The Week schedule has a function so you...

Страница 27: ...IT Consumption is calculated excluding external circulation pumps Size Mains voltage VAC Max consump kW Max consump A Max inc Cable mm Max fuse main supply A HERU 400 3 400 1 1 4 6 6 25 HERU 600 3 400...

Страница 28: ...ample shows a HERU T CX All terminals except for the feeding power connections are 2 level type 2 LEVEL CONNECTION TERMINALS Connection terminal beige Earth connection terminal green yellow The extern...

Страница 29: ...1 The supply air temperature sensor is intended to be mounted in the supply air duct circular or rectangular It is important that it is positioned after the last treatment module i e after any cooling...

Страница 30: ...air temperature sensor can be replaced with a room temperature sensor Connection of room temperature sensor as follows The connection cable of the extract air temperature sensor must be disconnected f...

Страница 31: ...mperature sensor Connection of outside air temperature sensor as follows The connection cable of the integrated outside air temp sensor must be disconnected from X3 M and replaced with the outside air...

Страница 32: ...ation due to power failure CONNECTION OF SPRING RETURN MOTOR If the damper motor turns the wrong way when starting the HERU CX flip the dam per actuator CONNECTION OF ON OFF MOTOR If the damper motor...

Страница 33: ...tion HEATING CP1 SV1 Connection of actuator and circulation pump as follows For activation configuration Parameter name Area Select Main index Con guration Con guration 1 Heating No Yes Yes Restart Ex...

Страница 34: ...d a freeze protection sensor must always be mounted on the water s return side If the water coil is mounted in a duct the freeze protection sensor with associated straps and contact paste must be moun...

Страница 35: ...ly mounted inside the HERU CX unit when delivered from H stberg AB If the electric heating coil is a duct design it is connected as follows GT9 is the designation for overheating protection For activa...

Страница 36: ...monitor with display enables active reading of differential pressure over the filter while retaining the monitor s alarm function It is delivered as the regular filter moni tor separately with a 5 met...

Страница 37: ...te Execute Main index Con guration Con guration 2 Pump cooling No Yes Yes exercise Yes Restart Execute Execute COMBI COIL DX COOLER AND HEAT PUMP DX CHP The system can control a combined cooling heati...

Страница 38: ...f reverse logic is required on output for DX CHP i e output active for heating Main index Unit Outputs Pump cooling Contact function NO NC NC CONFIGURATION WHEN INTEGRATED HEATER IS ELECTRIC Parameter...

Страница 39: ...th a timer push button At activation HERU CX is controlled to run at normal flow usually fan stage 2 For activation configuration Parameter name Area Select Main index Con guration Con guration 1 Filt...

Страница 40: ...F AUTO time channel If the time channel is set to OFF during the week schedule this will cause an external stop from BMS For only one control input read function and configuration according to Timer s...

Страница 41: ...operation EHC Quick stop is connected as follows For activation configuration Parameter name Area Select Main index Con guration Con guration 1 Filter alarm No supply air Combi Supply extract No Emer...

Страница 42: ...ngen Off Switched off Supply Comf Comfort mode Temperature setpoint comfort Economy Economy mode Temperature setpoint economy Osstp Not applicable for HERU CX Night cooling Night cooling enabled in op...

Страница 43: ...KNX Adjustable start up and regulator parameters Semi recessed mounting can be mounted on most types of recessed junction boxes Programmable schedule Connected directly on Climatix controller 2 wire i...

Страница 44: ...ple operation Corresponds to buttons UPS DOWNT and ENTER on the HMI for HERU CX Alarm button with LED Info button Connection via 2 wire interface to the controller Climatix process bus KNX supply volt...

Страница 45: ...ranges 1250 Pa or 2500 Pa QBM68 is also available for double sensors in a unit enclosure with the first sensor marked P1 and the second sensor marked P2 The following variants are possible Designatio...

Страница 46: ...Direct Direct FO not applicable to HERU CX Select Pressure regulation Restart Execute Execute Main index Con guration Con g IOs Pressure Flow Supply air pressure Pos Factor Area Com 500 Pa Type P401 S...

Страница 47: ...r the following reasons Rotation monitor Motor temperature Overvoltage Undervoltage Over under temperature control unit Short circuit Internal fault Connection diagram Functions Operation indication i...

Страница 48: ...ogram funct Stage Temp Setpoints for both fan stage and tempera ture comfort economy are controlled by the time switch program WEEK SCHEDULE Main index Unit Operating functions Time switch program Sch...

Страница 49: ...e later than the start date Weekday Choice x only day of the week Enter a day of the week Example Choice x Date Only the time for start is relevant Start Date 01 01 09 Result 1 January 2009 is an exce...

Страница 50: ...he password for level 4 2000 3 Change language if needed Main index System overview Language selection 4 Select Main index Configuration 5 Start Configuration 1 Connect with Restart 6 Continue with Co...

Страница 51: ...arameter settings page for the process bus for control panel and room unit TCP IP xxx xxx xxx xxx Address of controller on the bus Name of controller on the bus Go to the parameter settings page for i...

Страница 52: ...lave designed for communication to BMS Internal slave adr 0 247 Address of controller on the bus Internal settings RS485 Go to parameter page for RS485 settings TCP IP Go to parameter page for TCP IP...

Страница 53: ...ain text but only as a number See the tables on the following pages Double config IO Yes Double config IO 82 81 Double config IO pos DI3 External control input 1 and 2 allocated the same output DI3 Th...

Страница 54: ...Aux input DI 85 Pump return extra cooling DI 61 Acknowledgement reset of alarm DI 86 Alarm for extra DX cooling DI 62 Analogue outputs Name Type Position IO kont Name Type Position IO kont Frequency...

Страница 55: ...ing valve signal electric heater signal AO 0 10 V DC T2 X7 M SV1 X8 Cooling valve signal cooling unit signal signal HCP AO 0 10 V DC T2 X8 M SV2 KM1 HCP Expansion module 1 Physical positioning expansi...

Страница 56: ...t To return to the regular menu press ESC then choose Local connection to get to the Start menu GENERAL This chapter describes the following functions Alarm Alarm lists History lists Acknowledged alar...

Страница 57: ...itterat Kvitteras Kvitteras terst lls Kvitteras Larm normalt Larmindikering LED lyser Larmindikering LED blinkar Larmindikering LED blinkar 11 18 11 19 11 20 No No No No No Yes Yes Yes Alarm resetted...

Страница 58: ...LIST INFORMATION The alarm list contains the following information about the latest alarm Row 1 Alarm name Status Row 2 Input status Alarm class Row 3 Date Time Example Alarm electric heating 0 15 10...

Страница 59: ...59 START PAGE MAIN INDEX UNIT 11 23...

Страница 60: ...START PAGE MAIN INDEX SYSTEM OVERVIEW 60 START PAGE MAIN INDEX CONFIGURATION 11 24 11 25...

Страница 61: ...ally the function of the damper is to close the airways at the outside and exhaust air ducts when the unit is switched off It is important for operating and ener gy reasons that the dampers working pr...

Страница 62: ...ted to the drainage Check That the front surface of the coil is not dirty That the pump is running and that the water is circulating and has the correct temperature for the season Make sure the sensor...

Страница 63: ...or in the GP5 supply air duct so that it cannot be operated unless the fan is running Therefore do not switch off the voltage to the fan using the switch disconnector Instead use the control panel Not...

Страница 64: ...t the fan is rotating freely without scratching the inlet cone and that there is no noise from the bearings That all electrical cables are securely connected and that the protective casing is intact T...

Страница 65: ...berg AB recommends changing the filters at least two times a year If the filter locker is dirty That the filter locking is functioning properly That the filter seal strip is intact Action Remove the f...

Страница 66: ...ts the extract air from transfer into the supply air during rotation It is important for the blow out function that the extract air part has a greater under pressure than the supply air part There sho...

Страница 67: ...per pipes with aluminium slats For circulation and regulation of the water the heater is usually equipped with a shunt group To protect the heater from freezing a strap on freeze protection sensor is...

Страница 68: ...dle without lock HERU 400 1200 T S 994010003 Brush strip HERU 400 600 T S 993050122 Brush strip HERU 800 1200 T S 993050123 EC fan 315 1x230 HERU 400 T S 993080089 EC fan RH31V 1x230V HERU 600 T S 993...

Страница 69: ...Check the connectors on the extract air fan On some models the fan cabling for the extract air has a connector located next to the dividing line of the unit Power and signal are of different types so...

Страница 70: ...ted to the same output or input See chap 11 11 HMI Alarm Supply air pressure under range Extract air pressure under range PROC1 believes the pressure sensor for the supply air extract air pressure is...

Страница 71: ......

Страница 72: ...H STBERG AB Box 54 SE 774 22 Avesta Sweden Phone 46 226 860 00 E mail info ostberg com www ostberg com 1270466 utg 3...