Operating Instructions Sauna exclusiv 9kW    Page: 5

Setting counter timer

The   button serves the programming of the built-in counter timer.

1. Press the   button 

 the display will indicate 

Start time

10:25

.

2. By pressing the   and   buttons the desired turn-on time may be set.

3. Press the   again 

 the display will indicate 

Operation period

6:00

4. By pressing the   and   buttons the desired operation period may now

be set. The counter timer can only be activated (see above) after
programming an operation period.

To store the switching times, press the   button again. If you do not press
any button for more than 10 seconds during the setting process, then the
last displayed switching time is automatically stored and the normal
operating display will appear again.

Check list for probable malfunctions:

Any system components are factory-checked for their functions. Should any disturbances
occur even though, the following items should be checked, provided the proper installation
in any case, and whereas the connecting lines – soundly operated- need to be fixed
properly in the supply terminals.
1.)

Does the line voltage fit tightly between the supply terminals L1, L2, L3 and N ?

2.)

Has the temperature sensing system been fitted according to the fitting instructions?

3.)

In case of a malfunction of the control panel:
Keep the control at the constructional main switch
without voltage and check the fine-wire fuse for the
control electronic and the control panel. These are
situated inside the power component on the circuit
board.

 

Control

Control panel

4.)

If the heating does not work:
4.1.

In case of overheating the sauna cabin the thermal electric fuse which is
situated in the sensor casing in the cabin, will switch off the heating. After
cooling down it is not automatically switched on and the sensing system has to
be changed.
Checking the temperature fuses:

  Disconnect from the clamps 5 and 6 located at the power component, both

cable conductors of the red line.

 Measure the temperature fuse by using either a resistance meter or a

circuit continuity tester.

 

A defect temperature fuse does not show any conduction.

 

 

4.2.

 

For safety reasons the heating is automatically switched
off in the following cases: the temperature sensor is
defect, there has been an interruption or the sensing line

 

Sensor defect