Operating Instructions Sauna exclusiv 9kW    Page: 2

The power supply of the device has to be carried out by an universal-pole main switch
having a contact opening width of at least 3mm. 

Before opening the casing it is

absolutely necessary to discharge the device from voltage.

Electric connection:

The electric connection as well as all adjusting and service operations may only be
carried out by an approved electrical expert! The enclosed connection plans and the
current safety regulations in force are to be followed.

L3

L1

230V/max.200W

mains

fan

3x230V/max. 9kW

red - temperature fuse

white - temperature sensor

3N AC 400V

sauna heater 

W1

U1 V1

N N

L2

control

panel

1 2 3 4

5 6 7 8

1 2 3 4

230V/max.200W

N

U3

U2 N

M

light

Sauna exclusiv 9kW

16A

Should only one monopolar 230V mains supply be available, then the mains supply is to be
carried out according to the following connection diagram:

L3

L1

230V/max.200W

mains

fan

3x230V max. 9kW

red - temperature fuse

white - temperature sensor

1N AC 230V

sauna heater 

W1

U1 V1

N N

L2

control

panel

1 2 3 4

5 6 7 8

1 2 3 4

230V/max.200W

N

U3

U2 N

M

light

Sauna exclusiv 9kW

16A

To ensure a smooth distribution of the load among the three switching contacts in the
control device, the U1, V1 and W1 connector  must 

not 

be bridged in the control device.

The outer conductors are to lead separately to the heating coils. Please note that with a
monopolar feeding the zero conductor of the heating will carry the treble amount of current
of the outer conductors. 

This current must not be fed to the circuit board via the

clamps. 

The zero conductor of the heating has to be externally connected to the zero

conductor of the circuit feeding!
The electronic control is fused on the circuit board by a 0.16A fine fuse. In the control
device the connected consumers are not protected against short-circuit. The short-circuit
protection has to be ensured by suitable constructional fuses (max. 16A).
The power component is connected with the control panel by a four-conductor telephone
line  (osf-Art.Nr. 3100000500). The maximum length of the line is 30m.
Lines within the sauna cabin are to be heat resistantly equipped.