Installation and Operating Instructions 

-30 

-Vario

 

Filter control unit for speed-controlled pumps  

Part no. 310.000.0535 

 

 

Technical data: 

Dimensions: 

220mm x 220mm x 100mm 

Operating voltage 

230V/50Hz 

Power consumption of control unit: 

approx. 5VA (depends on 

operating mode) 

Switching capacity:  Pump: 

max. 8A / 1.0 kW (AC3) 

 

Heater: 

max. 3A / 0.4 kW (AC3) 

 

Dosing system: 

max. 3A / 0.4 kW (AC3) 

Degree of protection: 

IP 40 

Level sensors: 

Safety Extra Low Voltage (SELV) 

Ambient temperature: 

0-40°C 

Air humidity 

0-80% non-condensing 

 

Connectable pumps 

230V alternating-pump (rated current 
max. 8A) 

Speck ECO-Touch pump 

Speck ECO-Touch-Pro pump 

Speck Badu-90-ECO-VS pump 

Speck Badu-90-ECO-Motion pump 

Pentair IntelliFlo pump 

Pentair SuperFlo pump 

Zodiac FloPro VS pump 

UWE PMM pump 

Содержание Poolcontrol-30-Vario

Страница 1: ...hing capacity Pump max 8A 1 0 kW AC3 Heater max 3A 0 4 kW AC3 Dosing system max 3A 0 4 kW AC3 Degree of protection IP 40 Level sensors Safety Extra Low Voltage SELV Ambient temperature 0 40 C Air humi...

Страница 2: ...g mode 10 Controls on the front panel 11 LCD display 11 Operating mode selection 11 Pump indicator light 12 Heater indicator light 12 Heater switch 12 Solar heater indicator light 12 Solar heater swit...

Страница 3: ...ng slide valves and launched either manually or at a specific time or pressure While the filter pump is running the swimming pool heater is controlled by the electronic temperature controller During b...

Страница 4: ...in the front panel show when the filterpump and heater are running allowing easy checking of the status ECO mode can be started automatically on closure of the swimming pool cover limit switch termina...

Страница 5: ...be connected directly to the PC 30 Vario unit Connect the speed controller to terminals 15 20 There must be a link inserted between the two WSK terminals winding protection switch Always refer to the...

Страница 6: ...itching behaviour for the Stop function must be set to Stop when contact open oP Connecting a Speck Badu 90 ECO Motion pump A Speck Badu 90 ECO Motion pump can be connected directly to the PC 30 Vario...

Страница 7: ...be provided for the pump The power supply cannot be provided by the PC 30 Vario There must be a link inserted between the two WSK terminals winding protection switch Always refer to the operating ins...

Страница 8: ...t a NR 12 TRS 2 unit If the PC 30 Vario is intended to be operated without an NR 12 TRS 2 unit terminals 13 and 14 must be connected together with a link Disconnect the connecting cable before doing s...

Страница 9: ...31 sensor Solar 32 33 PC 30 Vario thermowell Connect the swimming pool temperature sensor to terminals 30 and 31 The temperature sensor is supplied as standard with a cable length of 1 5m If required...

Страница 10: ...setting the filter system is activated In this case the temperature controller regulates the heater to a target temperature of 3 C Fuses The electronic controller is protected by a 0 5A microfuse loc...

Страница 11: ...d Clear washing The filter pump is on because rinsing is in progress using the connected sliding valve Heater is disabled pump locked The filter pump is off because the winding protection switch has t...

Страница 12: ...e colour of the light indicates the heater operating mode off the heater is off green the heater is running red the heater is disabled You can use the button to switch the heater on or off Solar heate...

Страница 13: ...ss the button the day of the week flashes 6 You can now use the and buttons to set the day of the week To save the set time press the button again If no button is pressed during an interval of more th...

Страница 14: ...been programmed yet 2 After pressing either button or or if a switching time has already been programmed the display shows 0 00 0 00 1 and the minutes in the top time display flash switch on time Note...

Страница 15: ...you can press the button to adopt the current time pressing both and buttons at once deletes the cycle start time Pressing and holding the button for longer than 5 seconds will launch a backwash rinse...

Страница 16: ...ic text e g Filtersystem off Temp reached Water 23 0 Solar 38 4 Filter system operating mode Heater operating mode measured water temperature measured collector temperature Use the and buttons on the...

Страница 17: ...the set target temperature Solar heater on The solar heater is on because the water temperature is below the set target temperature and the collector is warmer than the swimming pool water Frost risk...

Страница 18: ...the display shows Solar dif off difference temp between water and collector 0 5 You can now use the and buttons on the terminal to change the temperature difference The lowest value you can set is 0...

Страница 19: ...particular heating system make sure it is displayed in the top line 1 After pressing the button on the terminal the filter system is switched off and the display shows Min heating s Min switching time...

Страница 20: ...value is saved automatically The filter pump run on is factory set to off run on time 0 Priority of temperature controller over timer Display text Heat priori This line displays whether the temperatu...

Страница 21: ...n now use the button on the terminal to enable priority mode and the button to disable it again 3 If you press the button again the standard diagnostics display reappears and the filter system resumes...

Страница 22: ...line of the Service Terminal 1 After pressing the button on the terminal the filter system is switched off and the display shows water frost Water temperature with freze protection 3 0 2 You can now...

Страница 23: ...play text In backwash This line displays how often a backwash operation using sliding valves has been launched Backwash counter external Display text Ex backwash This line displays how often a backwas...

Страница 24: ...fter pressing the button on the terminal the filter system is switched off and the display shows Filter pump OFF Pump can be operated manually 2 You can now use the and buttons on the terminal to swit...

Страница 25: ...tor ON Pump OFF Dosing equip OFF Filter pump OFF manual operating 2 You can now use the button on the terminal to switch on the dosing system and the button to switch it off again The filter pump is a...

Страница 26: ...correctly together If one of the sensors is replaced or a sensor lead is lengthened the system may need to be recalibrated using the Info button on the control unit Since the solar temperature control...