OSAKA

 - USER MANUAL - B4U - v2 - PAG. 1

 

 
 
 

 

 

B4U 

D Power Unit 

 
 
 

 
 
 
 
 
 
 
 
 
 

INTUITIVE CONTROL PANEL 

FOR REFRIGERATION

 

 

 

USER MANUAL - v1 

 

 
 
 

INTRODUCTION

 

 
 

This manual contains the information necessary 
for  the  correct  installation  and  instruction  for 
use  and  maintenance  of  the  product,  it  is 
recommended  that  you  read  it  carefully  and 
keep it. 

This  publication  is  the  exclusive  property  of  OSAKA 
SOLUTIONS, which prohibits reproduction and disclosure, even 
partial, unless expressly authorized. 
OSAKA  SOLUTIONS  reserves  the  right  to  make  aesthetic  and 
functional changes at any time and without prior notice. 
In  order  to  avoid  that  an  irregular  operation  of  the  B4U  or 
malfunction  can  create  dangerous  situations  or  damage  to 
people  or  things  or  animals,  it  is  recalled  that  the  installation 
must  comply  with and  take into  account  the  attached  security 
systems, necessary to guarantee said security.  
OSAKA  SOLUTIONS  and  its  legal  representatives  do  not 
assume  any  responsibility  for  damages  to  people,  things  or 
animals  derived  from  improper  handling,  improper  use, 
incorrect  use  or,  in  any  case,  non-compliance  with  the 
characteristics of the B4U. 

INDEX 

DESCRIPTION B4U 

1.1

 

GENERAL DESCRIPTION

 

1.2

 

DESCRIPTION DISPLAY B4U + POWER UNIT B4U

 

PROGRAMMING 

2.1

 

QUICK CONFIGURATION OF THE SET POINT 
“NORMAL”

 

2.2

 

STANDARD PARAMETER PROGRAMMING

 

2.3

 

PARAMETER PROTECTION THROUGH PASSWORD.

 

2.4

 

PARAMETER PROGRAMMING LEVELS

 

2.5

 

RESET THE FACTORY SETTINGS OF THE 
PARAMETERS

 

2.6

 

KEYBOARD LOCK FUNCTION

 

2.7 

VISUALIZATION OF THE VARIABLES 

USE WARNINGS 

3.1

 

PERMITTED USE

 

INSTALLATION WARNINGS 

4.1

 

MECHANICAL ASSEMBLY

 

4.2

 

ELECTRICAL CONNECTION

 

FUNCTIONING 

5.1

 

ON / STAND-BY FUNCTION

 

5.2

 

“NORMAL”, “ECONOMIC” AND “TURBO” OPERATING 
MODES

 

5.3

 

PROBE INPUTS AND DISPLAY CONFIGURATION

 

5.4

 

DIGITAL INPUTS CONFIGURATION

 

5.5

 

CONFIGURATION OF THE OUTPUTS AND BUZZER

 

5.6

 

TEMPERATURE REGULATION

 

5.7

 

COMPRESSOR PROTECTION AND START DELAY 
FUNCTION

 

5.8

 

DEFROST CONTROL

 

5.8.1

 

AUTOMATIC DEFROST

 

5.8.2

 

MANUAL DEFROST

 

5.8.3

 

DEFROST END

 

5.8.4

 

INTERVAL AND DURATION OF DEFROST IN CASE OF 
EVAPORATOR PROBE ERROR

 

5.8.5

 

DISPLAY LOCK IN DEFROST

 

5.9

 

EVAPORATOR FAN CONTROL 

 

5.10

 

ALARM FUNCTIONS

 

5.10.1

 

TEMPERATURE ALARM 

 

5.10.2

 

DIGITAL INPUT ALARM

 

5.10.3

 

DOOR OPEN ALARM

 

5.10.4

 

VOLTAGE CONTROL ALARM

 

5.11

 

KEYBOARD OPERATION “ON / OFF” AND “LIGHT”

 

5.12

 

ACCESSORIES

 

5.12.1

 

PARAMETER CONFIGURATION BY “KEY USB” ”

 

5.12.2

 

VIEWING THROUGH X2

 

5.12.3 

RS485 COMMUNICATION WITH “KEY TTL” 

PROGRAMMABLE PARAMETERS TABLE 

PROBLEMS, MAINTENANCE AND WARRANTY 

7.1

 

SIGNALING

 

7.2

 

CLEANING

 

7.3

 

WARRANTY AND REPAIR

 

7.4

 

DISPOSAL

 

TECHNICAL DATA 

8.1

 

FEATURES 

ELECTRICAL

 

8.2

 

FEATURES

MECHANICAL

 

8.3

 

FEATURES

FUNCTIONAL

 

 

 

1 - DESCRIPTION B4U  

 
1.1 - GENERAL DESCRIPTION 

The B4U model is an intuitive control panel that combines the Display 
B4U (Display) plus the Power Unit B4U (power unit). It has a digital 
microprocessor  that  can  be  used  for  temperature  control  in 
refrigeration applications. It is prepared for the ON / OFF control and 
defrost  control, at  intervals  of time,  to  reach  the  temperature  or  for 
the continuous operation of the compressor through the compressor 
stop, electrical resistance or gas inversion / hot cycle. 
The B4U has special functions to optimize defrost and functions that 
can be used to achieve energy savings in the system. 
The B4U has up to 4 relay outputs and 5 configurable inputs, of which 
3 are for NTC temperature probes and 2 are digital for voltage-free 
contacts. 

 

Содержание B4U

Страница 1: ...ONNECTION 5 FUNCTIONING 5 1 ON STAND BY FUNCTION 5 2 NORMAL ECONOMIC AND TURBO OPERATING MODES 5 3 PROBE INPUTS AND DISPLAY CONFIGURATION 5 4 DIGITAL INPUTS CONFIGURATION 5 5 CONFIGURATION OF THE OUTPUTS AND BUZZER 5 6 TEMPERATURE REGULATION 5 7 COMPRESSOR PROTECTION AND START DELAY FUNCTION 5 8 DEFROST CONTROL 5 8 1 AUTOMATIC DEFROST 5 8 2 MANUAL DEFROST 5 8 3 DEFROST END 5 8 4 INTERVAL AND DURAT...

Страница 2: ...be configured 3 DOWN AUX 2 key In normal operating mode pressing and releasing allows quick access to the Set Point selection and modification mode Pressing for 3 seconds allows activating deactivating the configured output configured as A2 anti fog heating elements In the programming and display modes of the temperature measured by the room probe the evaporator temperature P1 and P2 and in additi...

Страница 3: ...the PP parameter within the tS group To have this protection available we will program the desired password number in the PP parameter Once the protection is activated to access the parameter menu press the ON OFF LIGHT keys simultaneously for 5 seconds and the display will show rP press the LIGHT key and the display will show 0 At this point using the UP and DOWN keys we will establish the passwo...

Страница 4: ...hat instant To exit the variables display mode we will not press any of the 4 keys for approximately 10 seconds 3 WARNINGS FOR USE 3 1 PERMITTED USE The B4U has been designed as a measuring and regulating device in accordance with EN 60730 1 for operation at altitudes up to 2000m The use of the B4U in applications not expressly provided for in the aforementioned standard must include all appropria...

Страница 5: ...eople things or animals 4 2 1 ELECTRICAL WIRING DIAGRAM Color legend Cable Strip 1 Brown 2 White 3 Green 4 Blue 5 Red 6 Black 5 OPERATION 5 1 ON STAND BY FUNCTION The B4U once turned on can take 2 different conditions ON It means that it works with the normal control functions STAND BY It means that the controller does not operate with any control function and the display turns off the Stand by LE...

Страница 6: ...g the Et time it will automatically switch to ECONOMY mode The B4U remains in ECONOMY mode until the door is reopened or if configured until the tt timeout When it exits the ECONOMY mode the B4U performs a TURBO cycle to recover the temperature of the products then returns to the NORMAL operating mode and so on 1 The time Et is reset every time the door is opened In the case of the example the doo...

Страница 7: ...ATION OF THE OUTPUTS AND BUZZER The parameters related to the configuration of the outputs are contained in the group Ou The outputs of the B4U can be configured through the parameters o1 o2 o3 and o4 with the following functions ot Compressor Solenoid Control or Cooling Element dF Control of defrost heaters Fn Evaporator fans control Au Auxiliary output control En Allows the Control of a silencea...

Страница 8: ...with Heating action In this case the regulation Set point for the ot output will be SP SE SH while for the HE output it is through the Set SH The regulation differential for the ot output is the active one between d or Ed or Hd is assumed automatically by the B4U to have positive values in the cooling action while for the HE output the differential will be Hd considered with negative values during...

Страница 9: ...counts the time since the B4U was started This mode is the one currently used in refrigeration systems ct At intervals of compressor operation time The interval di is counted as the sum of the operating times of the output ot output on This mode is normally used in refrigeration systems with compressor stop in defrost cS Defrost cycle at each compressor stop The regulator starts a defrost cycle ev...

Страница 10: ...be set as EP exceeds the temperature set in parameter tE If this temperature is not reached within the time set in parameter dE the defrost will be interrupted To avoid unnecessary defrosting when the evaporator temperature is high the tS parameter allows setting the temperature referring to the evaporator probe below which the defrosts will be activated Therefore in the indicated modes if the tem...

Страница 11: ...nfigured with the o1 o2 o3 o4 parameters The buzzer can be configured to signal alarms by setting the parameter Bu 1 or 3 or 4 and always functions as an alarm that can be silenced This means that when activated it can be deactivated by briefly pressing any key Alarms can be configured to signal them by configuring the outputs The possible alarms that can be configured are the following On When yo...

Страница 12: ...e to show the initials oP on the display When the door open alarm intervenes the normally activated outputs fans or fans compressor are also deactivated 5 10 4 VOLTAGE CONTROL ALARM The parameters related to the voltage control alarm functions are found in the UA folder The B4U can automatically deactivate the control outputs when the mains voltage measured by the B4U through its power supply is l...

Страница 13: ...e SP S Parameters Relative to the Set Point 1 SH Turbo Set Point or Minimum Set point and Superheat Set point in HC mode 99 HS 4 0 2 SE Economic Set Point maximum set point LS 99 8 0 3 S1 Set Point SE SH 4 0 In i Parameters related to inputs 4 uP Measurement unit and resolution decimal point C0 C with resolution 1 F0 F with 1 resolution C1 C with 0 1 resolution F1 F with 0 1 resolution C0 F0 C1 F1...

Страница 14: ... 0 29 Ei Interval between defrosts in case of evaporator probe error oF 01 59 min 01 99 hrs 4 30 EE Defrost duration in case of evaporator probe error oF 01 59 sec 01 99 min 20 31 tS Temperature from which the defrost starts 99 9 9 9 9 10 99 C F 2 0 32 tF Temperature that forces the start of the evaporator defrost 99 9 9 9 9 10 99 C F 99 33 St Defrost start delay due to evaporator temperature oF 0...

Страница 15: ...1 2Y Temperature alarm type 2 see 1y 1 2 3 4 5 6 7 8 9 10 3 62 2H High temperature alarm setpoint 2 99 9 9 9 9 10 99 C F oF 63 2L Low temperature alarm setpoint 2 99 9 9 9 9 10 99 C F oF 64 2d 2H and 2L alarm hysteresis 0 0 9 9 30 C F 1 0 65 2t Alarm delay 2H and 2L oF 01 59 sec 01 99 min oF 66 2P Temperature alarm delay time 2 on connection oF 01 59 min 01 99 hrs 2 67 2A Action of alarms 2 on the...

Страница 16: ...ify the correct functioning of the probe it is useful to have the ohm values of the probes EP Possible anomaly in the EEPROM memory Press the SET key Turn the device off and on Err Fatal Device Memory Error Replace the device or send it in for possible repair 7 2 CLEANING It is recommended to clean the B4U only with a cloth slightly dampened with water or a non abrasive detergent and that does not...

Страница 17: ...MATE N LOK 250 removable connector Connection Display B4U Power Unit B4U 3 m MAX Through the cable with removable mini connectors Pollution degree 2 Ambient operating temperature 0 60 C Operating ambient humidity less than 95 RH non condensing Transport and storage temperature 25 60 C 8 3 FUNCTIONAL CHARACTERISTICS Temperature control ON OFF Defrost control by intervals or by temperature with elec...