Ormazabal velatia ekor.bat-200 Скачать руководство пользователя страница 5

IG-258-EN, version 02; 16/11/2018

5

General Instructions

ekor

.bat-200

Description and main characteristics 

1.3.2.  Battery charge

Battery charge starts following absence of alternating 
current voltage (AC) or after a battery test.

The battery charge process starts with fast charge state. 
The charger establishes a voltage setpoint (v_carga) and 
controls battery current to ensure it does not exceed 
maximum charge current (i_lim). Current is lost as the 
battery discharges. 

It switches from fast charge state to floating for either of the 
following two reasons:

1. 

The maximum time set for fast charge state (tlim_carga) 
is exceeded.

2. 

The battery current drops below a set threshold (i_flot).

Once the battery current drops below a minimum threshold 
(i_flot) or maximum time is exceeded (tlim_carga), it passes 
to floating state. In this state the charger establishes the 
battery float voltage (v_flot). Following a float time interval 
(t

min

_flot), it is taken that the battery is completely charged.

The unit remains in floating state until there is an absence of 
alternating current or a battery test starts.

The image below shows the typical charge process of a 
battery.

In order to extend the working life of the battery, battery 
voltage is compensated in accordance with temperature 
in floating state. A parametrisable variable (comp_flot) 
can be used to adjust the voltage to vary by each degree 
centigrade. 

The compensation range is limited between a maximum 
and minimum temperature (comp_t

min

 and comp_t

max

).

Temperature compensation (hab_comp) can also be 
enabled in fast charge state, and there is a voltage variation 
setting by degree (comp_carga). Enabling this option is only 
recommended when a study indicates that it is required.

1

Current (A)

2

Voltage (V)

3

Time

4

Fast charge at constant current 

5

Fast charge at constant voltage 

6

Floating

7

v_carga

8

v_flot

9

i_lim

10

i_flot

a

Voltage per cubicle

b

Charging current

Figure 1.2. 

Battery charge

1.3.3.  Battery discharge and disconnection

In the event of absence of alternating voltage, the batteries 
keep the equipment supplied for a specific time interval. A 
disconnection process starts if end of battery life is reached 
and the alternating voltage input is not restored.

The following operation guidelines are followed in the 
disconnection process:

•  The unit detects that battery life reaches its end using a 

parametrisable setting (desc_v_min) 

•  The "End of battery life" alarm is enabled at this moment.

•  If the AC input is not restored after a few minutes on 

standby, the unit disconnects the battery and both the 
unit and the connected charges therefore go off.

Apart from the normal discharge process, there are two 
other reasons for the battery disconnecting:

•  Minimum battery voltage (desc_inm). If it drops below 

this threshold, the battery disconnects instantaneously.

•  Maximum battery voltage (desc_v_max). If this level is 

exceeded, the battery disconnects for safety reasons. 

Содержание velatia ekor.bat-200

Страница 1: ...LIB ekor bat 200 Battery Charger General Instructions IG 258 EN version 02 16 11 2018...

Страница 2: ...ectrical installations Personnel must be fully familiar with the instructions and warnings contained in this manual and in other recommendations of a more general nature which are applicable to the si...

Страница 3: ...t or Impedance measurement 6 2 Characteristics 7 2 1 Electrical characteristics 7 2 2 Dielectric strength 7 2 3 Service conditions 8 2 4 CE Conformity 8 3 Tests 9 3 1 ekor bat 200 battery charger 9 4...

Страница 4: ...ut as shown in the image below 1 Input 2 Output 3 10 kV insulation 4 Phase 5 Neutral 6 AC 7 DC 8 24 48 Vdc 9 0 V 10 Earth 11 Chassis 12 Control 13 Alarms 14 Local signalling 15 Ethernet RS232 Figure 1...

Страница 5: ...ge to vary by each degree centigrade The compensation range is limited between a maximum and minimum temperature comp_tmin and comp_tmax Temperature compensation hab_comp can also be enabled in fast c...

Страница 6: ...ted and no more battery tests are carried out until this alarm is recognised The Battery failure alarm is grouped within the Urgent failure digital output 1 3 5 Fast test or Impedance measurement Thef...

Страница 7: ...nt 20 A Power factor 0 6 Rated power 200 W Maximum power 500 W Output range 48 Vcc 39 60 24 Vcc 18 30 V Table 2 1 Input characteristics The charger has four potential free contacts Parameter Remarks V...

Страница 8: ...requirements RoHS Directive 2002 95 CE Table 2 3 Service conditions For higher altitudes check with Ormazabal for the possible influence on equipment performance 2 4 CE Conformity This product compli...

Страница 9: ...terminals of each unit differential mode 1 kV EN 60255 5 Immunity Level Standard Electrostatic discharge Direct contact mode in metal equipment frames and connectors Level 4 8 kV EN 6100 4 2 Air mode...

Страница 10: ...nt peaks start up at rated power Level to be applied 12 A Mechanical tests Level Standard IP Protection grade Level to be applied IP20 EN 20324 IK Protection grade Level to be applied IK06 EN 50102 Vi...

Страница 11: ...230 Vac rms 2 AC input N phase X2 Alarms 1 Urgent failure alarm NC contact 2 Standalone end alarm NA Contact 3 Power failure alarm NA Contact 4 Non urgent failure alarm NA Contact 5 Alarms common X3...

Страница 12: ...d On Battery test failure end of battery s working life Red Charger ERROR Flashing Anomalies in charger Temperature sensor others On Temperature sensor failure Table 4 2 Description of the indications...

Страница 13: ...button is pressed for more than 3 seconds If there is a battery connected the charge process continues and the battery test failure alarm resets if it is enabled If there is no battery the urgent alar...

Страница 14: ...ETH1 port Access to the charger s webpage is via the ETH1 port both locally and remotely LOCAL IP 100 0 0 1 Remote IP Customised with the requested value Firefox browser version 26 is recommended for...

Страница 15: ...ltage in fast charge V V comp_carga Temperature compensation in fast charge mV C hab_comp Enables temperature compensation in charge 0 NO 1 YES i_flot Battery through current to float mA tlim_carga Ma...

Страница 16: ...esses IP Connexion IP for the SNTP protocol 20 char Gateway Gateway for the SNTP protocol SI_TFALL Time without synchronising in order to consider the internal clock out of sync min T_PETSINCRO Server...

Страница 17: ...oved and all the meters and the state machine restart always maintaining voltage without any interruption in supply 7 2 Hardware test This window can be used to force the state of the luminous indicat...

Страница 18: ...ery alarm is enabled meaning the urgent failure output and the Battery ERROR LED will be enabled 4 Position new batteries and make connections between them 5 Check that battery voltage is between 42 V...

Страница 19: ......

Страница 20: ...Subject to change without prior notice For further information contact Ormazabal Ormazabal Protection Automation IGORRE Spain www ormazabal com...

Отзывы: