IG-310-EN version 01; 31/03/2021
50
Operations sequence
General instructions
cpg
.0 lite: GIS medium-voltage switchgear,
gas insulated, up to 24 kV,
in accordance with IEC Standard
c.
Turn the lever ANTICLOCKWISE until final actuator
position is reached.
Figure 7.57.
Earthing switch open, after turning the lever
d.
Remove the operating lever. The selector switch
automatically returns to its central position.
Figure 7.58.
Final position after completing the operation
9.
Close the circuit-breaker:
a.
The spring charging status indicator shows
UNCHARGED. Move the access locking cover to the
right and insert the spring charging lever.
Figure 7.59.
Spring charging lever inserted