IG-310-EN version 01; 31/03/2021
20
Installation
General instructions
cpg
.0 lite: GIS medium-voltage switchgear,
gas insulated, up to 24 kV,
in accordance with IEC Standard
6.4.1. Recommended dimensions
Minimum recommended dimensions based on the trench
dimensions used in the tests in accordance with Standard
IEC 62271-200. The dimensions of the trench may vary in
accordance with the minimum radius of curvature of the
cables used.
Figure 6.4.
Trench dimensions
Minimum distances [mm]
Trench
Depth (e)
500*
Depth (f)
610*
(*) The dimensions of the trench depend on the characteristics of the
cables used.
Table 6.2.
Minimum recommended dimensions for the cable connection
trench