IG-310-EN version 01; 31/03/2021
49
General instructions
cpg
.0 lite: GIS medium-voltage switchgear,
gas insulated, up to 24 kV,
in accordance with IEC Standard
Operations sequence
7.
Open the circuit-breaker. Press the "O" pushbutton. The
circuit-breaker status indicator shows OPEN.
Figure 7.54.
Circuit-breaker open
8.
Open the earthing switch:
a.
Move the selector switch to the right, to earthing
switch position.
Figure 7.55.
Selector switch in earthing switch position
b.
Insert the earthing switch operating lever (YELLOW
knobs) in the earthing switch actuating shaft (area
marked with YELLOW line).
Figure 7.56.
Lever inserted in the earthing switch actuating shaft