Recommended sequence of operations
35
General instructions
cgmcosmos
system
Medium voltage switchgear and control gear, fully insulated in SF
6
gas up to 24 kV with external cable test device
IG-257-EN version 01; 03/02/2016
5.5.3 Isolating operation from the earthing position
Starting conditions:
earthing switch closed.
1.
Turn the selector to access the lever action area
anticlockwise.
Fig. 5.23
Selecting the operation using the selector
2.
Insert the lever in the earthing actuation shaft of the
earthing switch and turn anticlockwise.
Fig. 5.24
Process of turning the lever
3.
Remove the lever.
4.
The selector returns to its original position.
5.
Verify that the cubicle is in disconnected position.
Fig. 5.25
Detail of earthing switch open
1
2