Installation
15
General instructions
cgmcosmos
system
Medium voltage switchgear and control gear, fully insulated in SF
6
gas up to 24 kV with external cable test device
IG-257-EN version 01; 03/02/2016
Circuit-breaker function
Fig. 4.5
Dimensions of cable trench for
cgmcosmos
-v
Trench needed for the circuit-breaker function [“L” or “T” terminal 400/630 A]
Cable data
Guiding
radius of
curvature*
[mm]
Minimum depth
Cable
insulation
Cable type
Cable cross-
section [mm
2
]
Cable
diameter
[mm
2
]
D2
D4
Dry insulation
Single phase
150
38
500
550
550
185
42
600
650
650
240
42
300
48
750
800
800
400
48
Three phase
[7]
150
85
850
850
185
85
D2 for front (F) or rear (R) input.
D4 for side input.
* Each cable should be checked against the manufacturer's data.
Dimensions in mm.
For anti-vermin cubicles, the minimum value
of D2 will be the cable's curvature radius.
4.5 Fastening to the floor
Before assembling the cubicles, the floor must be carefully
levelled to prevent any deformation which may make
it difficult to connect it to the rest of the cubicles in the
assembly.
The cubicles can be fastened to the floor in two ways:
[4]
[7] For other types of cable sections, please contact
Ormazabal
.