Installation
23
General instructions
cgmcosmos
system
Medium voltage switchgear and control gear, fully insulated in SF
6
gas up to 24 kV with external cable test device
IG-257-EN version 01; 03/02/2016
3.
Put the cable compartment cover back in place
.
Fig. 4.24
Detail of front angular seal.
Three-phase cable with anti-vermin device
(example with feeder function)
1.
Connect the earthing switch.
2.
Access cable compartment
a. Remove front angular seal.
Fig. 4.25
Detail of front angular seal.
b. Remove the clamps from the cable support.
Fig. 4.26
Detail of the cable support clamp
c. Remove the rubber washer and cable inlets.
Fig. 4.27
Detail of the rubber washer and cable inlets.
Fig. 4.28
Detail of the removed cable inlet