Installation
13
General instructions
cgmcosmos
system
Medium voltage switchgear and control gear, fully insulated in SF
6
gas up to 24 kV with external cable test device
IG-257-EN version 01; 03/02/2016
Depending on the cubicle model, the accessory box
contains some of the following items:
• Ormazabal's
IG-257
General Instructions Document
•
Actuating lever
•
Spring-charging lever
•
Cubicle connecting kit:
ormalink
•
Springs
•
Syntheso grease
•
Earthing bar
•
End plug kit
•
Cubicle end assembly
•
Nylon thread
•
Plastic plugs
•
Side cover
•
Floor fastening assembly
4.3 Minimum installation distances
The minimum distances to the walls and ceiling to be
maintained in the installation are as follows:
a
Side wall
100
b
Ceiling
560
c
Front clearance
500*
d
Rear wall
>50**
(*) A minimum operation clearance of 1000 mm is recommended
** For functions v and 2lv. For function l d = 100 mm.
Fig. 4.3
Installation distances [mm]
The above-mentioned measurements
have been obtained in accordance with the
dimensions of the test compartment for gas-
insulated modules, according to annex AA of
standard IEC 62271-200.
The space required to extend the assembly with an
additional cubicle is 150 mm plus the width of the new
cubicle
[5]
.
[4]
[5] If in doubt, please consult
Ormazabal
.