RES-P3242GCL SERIES User’s Manual
94
LED Indicators In Front And Back
Power indicator
Green : Power LED x 2
System Ready Indicator
Green : Indicate system ready. Blinking for system is upgrading firmware.
Ring Master Indicator
Green : Indicate system operated in O-Ring Master mode
O-Ring Indicator
Green : Indicate system operated in O-Ring mode Blinking to indicate Ring is broken.
Fault indicator
Amber : Indicate unexpected event occurred
10/100Base-T(X) RJ45 port indicator
Green at left for port Link/Act. Amber at right for 100Mbps indicator
10/100/1000Base-T(X) RJ45 port
indicator with combo port
Green at down for port Link/Act
1000Base-X SFP port indicator with
combo port
Green at up for port Link/Act
Fault Contact
Relay
Relay output to carry capacity of 1A at 24VDC
Power
Redundant Input power
Dual 12 ~ 36VDC power inputs
Dual 36 ~ 72VDC power inputs
Dual 88 ~300VDC/100 ~ 240VAC
power inputs
Power consumption (Typ.)
18 Watts
Overload current protection
Present
Present
Present on terminal block
Physical Characteristic
Dimension (W x D x H)
443.7(W) x 262.7(D) x 44(H) mm (17.46 x 10.34 x 1.73 inch)
Weight (g)
TBD
TBD
3890 g
Environmental
Operating Temperature
-40 to 85
o
C (-40 to 185
o
F )
Operating Humidity
5% to 95% Non-condensing
Regulatory Approvals
Power Automation
IEC 61850-3, IEEE 1613
EMI
FCC Part 15, CISPR (EN55022) class A, EN50155 (EN50121-3-2, EN55011, EN50121-4)
EMS
EN61000-4-2 (ESD), EN61000-4-3 (RS), EN61000-4-4 (EFT), EN61000-4-5 (Surge), EN61000-4-6 (CS),
EN61000-4-8, EN61000-4-11
Warranty
5 years