Connection
11
5
Connection
This chapter explains the connection method of the
NETC01-M2
and power supply/communication cable, as well as
the grounding method.
For protection against electric shock, do not turn on the power supply until the wiring
is completed.
5-1
Connection example
RS-485 communication
cable
MECHATROLINK-II
communication cable
24 VDC
GND
Grounding
Power supply connector (CN1)
MECHATROLINK-II
communication
connector (CN2-1)
RS-485 communication
connector (CN6)
Data edit connector (CN3)
OPX-2A
Use the
MEXE02
or
OPX-2A
to set parameters.
MEXE02
Or
Use the accessory communication
cable for the support software when
connecting the PC and
NETC01-M2
.
5-2
Connecting the power supply and grounding the
NETC01-M2
Connecting the power supply
Connect the power supply cable (AWG22: 0.3 mm
2
) to the power supply connector (CN1) of the
NETC01-M2
using
the included CN1 connector (3 pins).
Grounding the
NETC01-M2
Ground the Frame Ground terminal (FG) of the
NETC01-M2
as necessary.
Ground using a wire of AWG24 to 16 (0.2 to 1.25 mm
2
), and do not share the protective earth terminal with a welder or
any other power equipment.
CN1 connector pin assignments
Pin No.
Signal name
Description
1
+24 VDC
+24 VDC 0.2 A or more
2
GND
Power supply GND
3
FG
Frame Ground