Connection
▌
26
6-4
Connecting to the power supply
Connect the power cable to the power supply terminals located on the driver.
For single-phase 100-115 V unit, single-phase 200-230 V unit
Connect the live side of the power cable to the L terminal and the neutral
side to the N terminal.
Connect the FG terminal to the grounding point of the power supply.
Use a power supply capable of supplying the current capacity as shown
below.
FG
Lineard motor model
Current capacity
Single-phase 100-115 V
Single-phase 200-230 V
LAS2B(F)90
LAS2B(F)500
LAS4B(F)40
3.2 A or more
3.7 A or more
LAS4B(F)500
4.1 A or more
4.5 A or more
For three-phase 200 V unit
Connect the U, V and W phase lines of the three-phase 200 V power
cable to the L1, L2 and L3 terminals, respectively.
Use a power supply capable of supplying the current capacity as shown
below.
Lineard motor model
Current capacity
LAS2B(F)90
LAS2B(F)500
LAS4B(F)40
2.0 A or more
LAS4B(F)500
2.4 A or more
Terminal screw size and applicable lead wire size for power connection
Use a round terminal for power connection.
•
Screw size: M3
•
Tightening torque: 0.8 N·m (113 oz-in)
•
Applicable minimum lead wire size: AWG18 (0.75 mm
2
)
9 (0.35) or more
6.2 (0.24) or less
9 (0.35) or more
6.2 (0.24) or less
3.2 (0.13) or more
Ø3.2 (Ø0.13) or more
Unit: mm (in.)
•
Furnish a power supply capable of supplying adequate driver input current. If the current capacity
is insufficient, the transformer may be damaged, or the lineard motor may run erratically due to a
drop in torque.
•
Do not run the driver’s power cable through a conduit containing other power lines or motor
cables.
•
After shutting down the power, wait at least 10 seconds before turning it back on, unplugging, or
plugging in the motor’s cable connector.