36
Please note that the return air is not zoned and the 70% rule does not apply here.
If the required exhaust air capacity is higher than 70% of the supply air capacity,
this capacity must be entered on the unit.
Setting device capacity
Step 1 Close the windows and doors.
Step 2 Open the exhaust and supply valves to the maximum. Step 3
Unplug the balanced ventilation unit from the mains supply.
Step 4 Unscrew the 2 screws on the top of the circuit board cover using a Torx
screwdriver (T25). The PCB cover can then be removed from the
device housing, and the DIP switches on the PCB are now accessible.
Note: Carefully open the cover to avoid disconnecting the
cable from the display. If the cable comes loose, replace it in
the connector next to the dipswitches.
Step 5 Set the desired unit capacity for both fans using the DIP switches
for position 1, 2 and 3.
next page. When adjusting the zones, the highest setting is used.
Step 6 Restart the HRC.
Step 7 Distribute the set flow rate to the two connected zones.
See chapter 6.2.
Step 8 Adjust the supply valves for both zones separately.
Please refer to the description in chapter 6.3.
Step 9 Adjust the drain valves of both zones simultaneously. Both zones must
be open. Ensure that sufficient overflow facilities are available.
Содержание 22001090
Страница 1: ......
Страница 2: ...2...
Страница 6: ...index 6...
Страница 16: ...index 16...
Страница 27: ...index 27...
Страница 58: ...index 58 17 Perilex cable HRC 22915405 18 Side earthed cable HRC 22915426...
Страница 60: ...index 60 Only suitable for controlling ventilators U FL R SMT 1 Antenna connector Transformer...
Страница 66: ...index 58 12 400 150 62 126 0 32 13 400 250 79 160 0 40...
Страница 69: ...index 61 Date Activity Initials Overview of maintenance operations Registered RF components Other remarks...
Страница 74: ...Landjuweel 25 3905 PE Veenendaal PO Box 416 3900 AK Veenendaal t 31 0 318 54 47 00 info orcon nl www orcon nl...