Provide a suitable power source with electrical overload protection to meet the power
supply input voltage range of 100-240 VAC, 50-60 Hz. The power source must not be
overloaded by the total number of disk shelves in the cabinet.
■
The power source must provide a reliable earth connection for each disk shelf and the
cabinet.
■
Ensure that the power source is easily accessible because the power cord is the main
disconnect device for the disk shelf.
Plug a power cord into each power supply with fan module.
Plug the other end of the power cords into the external power source for the cabinet.
Note:
To guarantee redundancy, power cords must be connected to two separate and
independent power sources.
Apply power to the external power source.
Place the power supply on/off switches to the
"
I
"
on position.
Turn on the cabinet circuit breakers, if applicable.
After the disk shelf powers on, which could take several minutes, ensure that the system power
indicator on the front of the disk shelf is lit a steady green, and that each power supply with fan
module status indicator on the rear is lit a steady green. If not, power off the disk shelf as
described in the next section and reseat the faulted module. If the module status indicator is not
a steady green after module reinsertion, contact Oracle Customer Service.