Install the Right LED/USB Indicator Module
208
Oracle Server X5-2L Service Manual • May 2015
■
If your server is configured with twelve 3.5-inch storage drives or twenty-
four 2.5-inch storage drives, perform the following procedures.
a.
Install the four No. 2 Phillips screws (two on each side of the chassis)
that secure the disk cage assembly to the server chassis.
FIGURE 78
Installing the Disk Cage Assembly Screws
b.
Install the server front fan assembly door.
See
“Install the Fan Assembly Door” on page 228
.
■
If your server is configured with eight 2.5-inch storage drives, install the
server disk cage cover.
See
“Install the Disk Cage Cover” on page 229
.
7.
Return the server to operation.
a.
Install the server top cover.
See
“Install the Server Top Cover” on page 226
.
b.
Return the server to the normal rack position.
See
“Return the Server to the Normal Rack Position” on page 231
.
c.
Reconnect the power cords to the power supplies, and power on the server.
Содержание X5-2L
Страница 1: ...Part No E48333 04 May 2015 Oracle Server X5 2L Service Manual ...
Страница 2: ......
Страница 12: ...12 Oracle Server X5 2L Service Manual May 2015 ...
Страница 24: ...24 Oracle Server X5 2L Service Manual May 2015 ...
Страница 50: ...50 Oracle Server X5 2L Service Manual May 2015 ...
Страница 69: ...Remove the Disk Cage Cover From the Server Preparing for Service 69 Install the Disk Cage Cover on page 229 ...
Страница 70: ...70 Oracle Server X5 2L Service Manual May 2015 ...
Страница 100: ...100 Oracle Server X5 2L Service Manual May 2015 ...
Страница 268: ...268 Oracle Server X5 2L Service Manual May 2015 ...
Страница 292: ...292 Oracle Server X5 2L Service Manual May 2015 ...