Locate an eUSB Drive
Locate an eUSB Drive
From the OpenBoot PROM, type:
ok
probe-scsi-all
.../pci@300/pci@1/pci@0/pci@2/usb@0/[email protected]...
1112
...
Related Information
■
“Determine if an eUSB Drive is Faulty” on page 104
■
“Identifying Components” on page 13
■
“Install the eUSB Drive” on page 106
■
“Remove the eUSB Drive” on page 105
Determine if an eUSB Drive is Faulty
1.
Check to see if any Server Service Required LEDs are lit or flashing.
See
“Front Panel Components (Service)” on page 17
“Interpreting LEDs” on page 30
2.
In Oracle ILOM, verify that the eUSB drive is recognized and check the
fault_state.
->
show/SYS/MB/EUSB_DISK/
./SYS/MB/EUSB_DISK
....Targets:
....Properties:
....type.=.Flash.Mini-Disk
....fault_state.=.OK
....clear_fault_action.=.none)
....Commands:
....cd
....set
....show
...
->
3.
Use the Oracle ILOM
faultmgmt
shell or the
fmadm faulty
command to identify a
faulty component.
104
Netra SPARC S7-2 Server Service Manual • February 2017
Содержание Netra SPARC S7-2
Страница 1: ...Netra SPARC S7 2 Server Service Manual Part No E73207 03 February 2017 ...
Страница 2: ......
Страница 12: ...12 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 24: ...24 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 42: ...Server Fault Remind Button Operation 42 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 84: ...84 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 108: ...108 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 140: ...140 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 150: ...150 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 158: ...158 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 192: ...192 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 216: ...216 Netra SPARC S7 2 Server Service Manual February 2017 ...
Страница 258: ...258 Netra SPARC S7 2 Server Service Manual February 2017 ...